Page 48 - IOM / ROOFTOP BALTIC Series - 0
8
03 - E
HEATING: gas burner
BURNER SAFETY CHECKS
Smoke extractor pressure switch Test.
- With the gas burner running, disconnect the flexible tube
fitted to the pressure taping on the pressure switch (fig. 65).
- The Flame must disappear and the extraction fan must
carry on running.
- However, NO fault will be displayed (Gas ignition control
block or CLIMATIC).
- After reconnecting the tube, the Burner will restart after a
period of 30 to 45 seconds pre-ventilation.
Gas pressure switch test
-With the gas burner running, close the shut off valve
located before the rooftop.
-The burner stops completely.
-However, No fault light will be displayed on the Gas ignition
control block.. After 6 Minutes, the CLIMATIC will display a
fault.
-Reset the CLIMATIC.
I
onisation Probe test
-With the gas burner running, disconnect the terminal plug
coming from the ionisation probe to the gas ignition control
box.
-The flame disappears
-The fan is still running and attempting to restart the burner
(restart cycle 30 to 45 seconds).
-if the ignition probe is not reconnected at the end of the
ignition sequence the burner will stop completely.
-The fault light on the gas ignition control block is ON.
-Manually reset the gas ignition control block to eliminate
the fault.
IN CASE OF PROBLEMS REFER TO THE START UP
SEQUENCE FLOWCHART NEXT PAGE
Fig. 65
Fig. 66
Fig. 67
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...