IOM / ROOFTOP BALTIC Series - 0
8
03 - E Page 95
maintenance diagnostic
FAULT
HP PROBLEMS
AND HP CUT OUTS
Strong variations of
pressure ( 2 to 3
bar) Thermostatic
Expansion Valve
"hunting"
Very high discharge
temperature,
High amps
measured at
compressor
POSSIBLE CAUSE AND SYMPTOMS
Moisture or contaminants in the system
Condenser coil is obstructed
Recycled Hot Air
Incorrect adjustment of the expansion valve
Low refrigerant charge
Filter drier obstructed with gas bubbles at the
expansion valve inlet
Moisture in the system
Very high superheat, very hot compressor
Four Way reversing valve possibly blocked,
abnormal noise from the valve, low LP and
increasing HP
SOLUTION
If the circuit pressure is higher (<1bar) than the
saturated pressure corresponding to the
measured outdoor temperature, there is
possibility that some contaminants are present in
the system.
Reclaim the refrigerant, and vacuum the circuit
(Ensure very low and slow vacuum for R407c)
Recharge the unit
Check the condenser coil and clean is necessary
Check clearance around the condenser
Refer to LP problems and LP cut out section
Open the superheat adjustment on the expansion
valve.
Check the pressure drop on the filter drier in the
suction line
Check operation of the valve by going through
cycle inversions. Change if necessary.
Refer to LP problems
INDOOR FAN BLOWER
REFRIGERATION
FAULT
High amps on
action Fan motor
High amps on
reaction Fan motor
Unstable running
and high vibration
POSSIBLE CAUSE AND SYMPTOMS
Pressure drop in the ducting installation too low.
Pressure drop in the ducting installation too high.
Fan jumping from one operating point to
the other.
SOLUTION
Reduce the rotation speed of the fan
Measure and estimate the airflow and pressure
and compare with the specification from
customer.
Reduce the rotation speed of the fan
Measure and estimate the airflow and pressure
and compare with the specification from
customer.
Change rotation speed of the fan.
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...