Page 50 - IOM / ROOFTOP BALTIC Series - 0
8
03 - E
HEATING: gas burner
GAS BURNER TROUBLESHOUTING
If faults reported on CLIMATIC
-Reset the CLIMATIC.
-Check voltage: 230V after circuit breaker.
-Check GAS isolation shut-off valves are open.
-Check GAS pressure at the inlet of the GAS valves. It must be >20 mbar when the Burners shut down.
-Adjust the set points to priorities the burner. Increase the value of the room temperature set point to a temperature higher
than actual room temperature.
STAGE
NORMAL
POSSIBLE
ACTION
POSSIBLE
OPERATION
FAULT
SOLUTION
Heating
Contactors
Contactors do
+ Check "Safety Thermostats" In the air flow
Replace
Requested
engaged
not engage
before the gas heat exchanger.
component
+ Check the free movement of the fan wheel
+ Check the supply temperature limitation thermostats
+ Replace thermostat
Contactors
Extraction Fans
+ Check gas low pressure switch
+ Open gas supply
are
are
Nothing
+ Check electrical connection on the gas
+ Replace connection
engaged
running
happens
Ignition Control Block and on
board if necessary
connection board
+ Check the fan voltage supply voltage
+ Check the fire-up electrode
+ Re-position the pressure
After 30 to 45
Continuous
+ Check the pressure drop at the pressure
switch tube
Extraction
seconds :
ventilation
switch : It must be higher than
165 Pa
+ Change the pressure
fan is
pre-ventilation the
happens
+ Check the good operation of the pressure
switch
ON
fire-up electrode
without sparks
switch using an Ohmmeter and by artificially
+ Reset or replace the
should spark
from fire-up
creating a depression in the tube.
Thermostat
electrode
+ Check the operation the Backfire thermostat.
+ Remove the air from the
Continuous
After a few
After 4 seconds
+ Check injection pressure during start-up
gas pipe-work
ventilation
seconds the
the GAS burner
(value for High Heat)
+ Adjust the injection
and sparks
gas burner
still not operating
+ Check the supply voltage to the ignition
pressure to high heat value.
from fire up
fires-up
and safety shutdown control box (continuous voltage)
+ Change the control box
electrode
by the ignition
+ Remove the control box from the gas block.
if the gas valve is OK.
Control Block.
+ Change the gas valve.
Within 4 seconds
+ Check that the High / Low control is
the GAS burner
connected (for valve VK 4125 P).
+ Check the whole
fires-up BUT
+ Check the position and connections of the
electrical supply.
safety shutdown
Ionisation Probe. It must not be Earthed (230 V) + Adjust the supply and
from the ignition
+ Check the Polarity of the 230 V connection
injection pressure if gas is
Control Block.
on the gas burner transformer.
different from natural
+ Measure the Ionisation Current : It must be
gas G20 : ( G25 gas of
higher than 1,5 microAmps.
Groningue for example).
+ Check the type of gas.
Table 6
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...