Page 58 - IOM / ROOFTOP BALTIC Series - 0
8
03 - E
22˚C
26˚C 27˚C 28˚C 29˚C 30˚C 31˚C 32˚C 33˚C 34˚C
23˚C
24˚C
25˚C
26˚C
27˚C
28˚C
Set
Point
Dynamic Set point : 6°C
Outdoor Temperature
control software features
Forced modes
3 hours Override
A three hours override period can be forced on the
CLIMATIC
TM
50:
With this feature, a new room temperature set point and
fresh air requirement can be imposed for a three hour
period; It will then revert to the original setting at the end of
the override period or earlier by switching off the override on
the controller display.
Forced unoccupied zone.
The unoccupied zone settings can be forced for a period of
up to seven days. It will then revert to the original settings at
the end of the defined period or earlier by switching off the
forced unoccupied mode on the controller display.
Heating priorities
It is possible to set heating priorities depending on the
outdoor temperature.
Example:
It could be decided based on energy costs, that on a dual
fuel unit, it should run in heat pump mode when the
temperature is above 0°C and switch to gas burner below
that point.
OTHER FEATURES
Dynamic Set Point
This feature allows the set point to change according to the
outside temperature.
Example:
If the set point is 25°C
And the dynamic set point is set to 6°C
Then, when the outdoor temperature reaches: 31°C (25°C +
6°C) the set point will follow the outdoor temperature with a
6°C temperature difference.
If you do not want to use this feature, set the dynamic set
point to 99
Time Zones and scheduling
With the Climatic50 the scheduling has been completely
reviewed:
The first day of the week is Monday.
Automatic switch from winter time to summer time.
Unoccupied mode from one to seven days
Three occupied and one unoccupied zone per day
For each zone a series of set points and feature can be
adjusted or selected, depending on the type of display which
is being used.
LIST OF SET POINTS
CONFORT
SERVICE
PER ZONE
DISPLAY
DISPLAY
AMBIANT TEMPERATURE
Yes
Yes
Average set point
Dynamic Set Point
Yes
Yes
Cooling Set Point
0
Yes
Heating Set point
0
Yes
Heating Priority
0
Yes
FRESH AIR REHEAT
activated
0
Yes
Heating priority
0
Yes
HUMIDITY
Dehumidification
0
Yes
Humidification
0
Yes
AUTHORIZATION
Free Cooling
0
Yes
Fresh Air by CO2
0
Yes
Mechanical cooling
0
Yes
Mechanical heating
0
Yes
Auxiliary heating
0
Yes
OTHER
Fan Mode :On / Off / Auto
0
Yes
Minimum fresh air (%)
Yes
Yes
SCHEDULING
Beginning of the zone for each day
Yes
Yes
Each zone is determined by its starting time.
REACTIVITY : 3
DELTA +5
15%
75%
100%
DELTA +3
9%
45%
90%
DELTA +1
1%
15%
30%
1MIN
5MIN
10MIN
REACTIVITY : 6
DELTA +5
30%
100%
100%
DELTA +3
18%
90%
100%
DELTA +1
2%
30%
60%
1MIN
5MIN
10MIN
8h00
12h00
14h00
20h00
Table 9
Table 10
Fig.85
Table 11
Table 12
Monday
Unoc.
ZA
ZB
ZC
Unoc.
Tuesday
Wed.
Thursday
Friday
Saturday
Sunday
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...