IOM / ROOFTOP BALTIC Series - 0
8
03 - E Page 47
HEATING: gas burner
PRESSURE ADJUSTMENTS ON HONEYWELL
PRESSURE REGULATING VALVE TYPE VK 4105
Pressure regulator adjustment with 300mbar gas
supply:
- The Burner must run in High Heat mode for this check.
- Place the tube of the "accurate" manometer on the Inlet
pressure port (figure 61) of the Gas Regulating Valve after
having loosened the screw by two turns.
- Check and adjust if necessary the valve Inlet pressure to
20.0 mbar (G20) or 37.0 mbar for propane (G31) or 25 mbar
for Groningue (G25).
High Heat Injection Pressure Checks
- Place the tube of the "accurate" Manometer to the OUT
port on the Gas injector support bar after having loosened
the nut.
LOW HEAT
ADJUSTMENT
HIGH HEAT
ADJUSTMENT
UNDERNEATH
Check and adjust if necessary the valve OUTLET pressure
to 8.4 mbar (G 20) / 31.4 mbar for propane (G31) and
12.3mbar for Groningue (G25).
Low Heat Injection Pressure Checks
- Switch the control to Low Heat
- Check and adjust if necessary the Outlet pressure to 3.5
mbar (G20) or 14 mbar for propane (G31) and 5 mbar for
Groningue(G25).
- Re-tighten all pressure adjustment screws and nuts.
Pressure adjustments table for each type of gas
Category
Supply
Low Heat
High Heat
pressure
injection
Injection
G20
20.0 mbar
3.5 mbar
8.4 mbar
G25
(Groningue)
25.0 mbar
5.0 mbar
12.3 mbar
G31 (GPL)
37.0 mbar
14.0 mbar
31.4 mbar
INLET
PRESSURE
MEASURING
PORT
Fig. 61
Fig. 62
Fig. 63
Fig. 64
Table 5
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...