Page 98 - IOM / ROOFTOP BALTIC Series - 0
8
03 - E
MAINTENANCE PLAN
TA
S
K
Clean or replace filters: Disposable, or met
al frame.
V
isual check of the oil level
Position check of the compressor crankcase heater
.
Belt tension check.
Centrifugal fan bearings check
Check absorbed
Amp
s
Check Smoke detector
Check Climatic control, set-point
s and
variables
Check clock settings
Check the position and tightness of refrigeration component
s
Check
Airflow rate safety switch (if fitted).
Check freeze protection on HWC
Check three way valve on HWC
Check economiser actuator operation
Check refrigeration 4way valve
Check tightness of all electrical connec- tions
OPERA
TING MODE
Replace filters with new ones if disposable. V
acuum clean or
blow the dirt. W
ash and dry carefully
. +Replace media if
necessary Blocked filter will reduced the performance of the unit. THE UNIT
MUST
NOT
OPERA
TE WITHOUT
FIL
TERS
V
isually check the oil level through the sight glass on the side of
the compressor casing
Check the heating resist
ance is fitted properly and tight around
the compressor body
.
Check belt tension (Info in IOM) Replace belt if necessary
.
Isolate unit from the main power supply; Push the fan wheel manually and check for abnormal noises. Bearings are lubricated for life but may need replacement af
ter 10000 hours
Check absorbed
Amp
s on all three phases; comp
are with the
nominal value given in the electrical wiring diagram.
S
tart the unit.
T
rigger the smoke detector by moving a magnet
around the detector head. Reset unit and control.
Refer to the commissioning sheet; Check all set point
s are set
according to this document.
Check the time and date of the control
Check systematically all connections and fixings on the refrigeration circuit. Check for oil traces, eventually a leak test should be conducted. Check operating pressures correspond to the ones indicated on the commissioning sheet
Shut down supply fan.
The fault must be detected within 5
seconds.
Increase room set-point 10°C above the actual room temperature. Check operation of the piston. It must move away from the valve head. Reset the control.
Check all fixings and transmission. S
top the unit using the
control.
The fresh air damper must closes. S
tart the unit the
fresh air damper should open
With the unit running in cooling mode increase the room set- point temperature by 10°C.
The unit should switch to heat pump
mode. Reset the control.
Power down the unit and check and tighten all screws, terminal and electric connections, t
aking a p
articular attention to the
power lines and low volt
age control wires
6
YEARL
Y
E
S
T
IM
A
T
E
D
MONTHL
Y
QUARTERL
Y
M
O
N
T
H
LY
B
4
T
IM
E
WINTER
(mn)
0
20
0
2
0
2
0
10
0
10
∆
15
∆
5
∆
15
05
∆
30
0
∆
5
∆
5
∆
5
∆
5
∆
30
Table 1
6
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...