IOM / ROOFTOP BALTIC Series - 0
8
03 - E Page 41
VENTILaTION : FANSTART
Current protection of the Thyristor
The FANSTART will display a fault (red LED) if the current
exceeds the thyristor current limits
125A during 0.4s
87.4A during 2s
75A during 6s.
62.5A during 20s.
Start up sequence too long
A fault (red LED) will appear if after 1min20s the FANSTART
Control is not bypassed and the motor running from the
mains.
Phase rotation check
If the phase rotation is incorrect the FANSTART Control will
display a fault ( Red LED). Two of the phases must then be
inverted and the start up cycle resumed.
AIR SOCK CONTROL
FANSTART OPERATION
The use of air socks for space conditioning allows high air
volumes to be distributed at low velocity and is becoming a
common feature in many applications. To accommodate this
trend, Air-sock control is offered which allows the air socks
to be progressively filled with air on start up. BALTIC has
been enhanced with an electronic device to soft start the
fan. It takes up to 1 minute to go from 0% of air to full air
flow.
This time can be divided in several stages:
- The aim of this first voltage input is to overcome the
resistance of the transmission (Pulleys and belts): 0.5s and
up to 1000 rpm
- The second stage is to inflate the air sock: 5 to 30s. and
600 to 900 rpm
Finally the air sock is gradually pressurised during the last 5
to 30 second. The motor reaches nominal speed and the
controller is bypassed.
The motor speed control is achieve through a variation of
the supply voltage of each phase at constant frequency.
The thermal overload limit on the motor imposes a current
limitation during the acceleration stage. Hence if the
selected slope is to steep, a predefined current limit can be
reached (potentiometer adjustment) and the controller will
automatically reduce the voltage set-point accordingly. Then
once the current is back under the high current limit it
carries on with the start up cycle.
Safety
Excessive "slow down" limit
The FANSTART will display a fault (red LED) and stop the
motor, if the motor slows down excessively (voltage could
reach 0V) because of the current limitation during the
acceleration stage.
Missing phase safety
The FANSTART will display a fault (red LED) if the current
in the third phase is too low or reaches 0 Amps (Three
phase supply or motor problem)
Current
1
st
voltage Input to Overcome
transmission
resistance
Over-current limit
Air sock
Inflation
5 to 30s Acceleration 15 to 30s
FANSTART off
FAN START
OFF
MOTOR OFF
Green LED = 0
Red LED = 0
MOTOR OFF
Green LED = 1
Red LED = 1
Power + Control ON
Green LED = 1
Red LED = 0
Control ON
Power OFF
PHASE
ROTATION
CHECK
T°C Fault
Thyristor
OK
INFLATION
Green LED = 1
Red LED = 0
ACCELERATION
Green LED = 1
Red LED = 0
(If current control ON)
CONTROL OFF
motor connected
to mains
NOT OK
I > I max
Speed = 0
T > 1 min20s
I < Imin
I > I max
Speed = 0
T > 1 min20s
I < Imin
Fig. 43
Fig. 42
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...