IOM / ROOFTOP BALTIC Series - 0
8
03 - E Page 81
Confirm by clicking on «Submit»
PROBLEM SOLVING
Impossible to enter your access code, you remain
on the welcome page.
Local communication has been interrupted. You must
restart the local unit.
After restarting, you must wait for 5 to 10 minutes until the
unit is ready to be queried once more.
The values read do not seem to move.
The values are not in fact refreshed automatically, and for
all the pages you must use the Refresh function to be sure
you are reading the latest values.
The keyboard has disappeared from the task bar.
Click on Start / Programs / StartUp
The local unit is not answering the phone
The local unit is - or was - powered down, and you must
press the On/off button. See recommendations at the
beginning of the document.
The unit is not connected to a direct analogue phone line.
How to check the ClimaLink is functioning correctly after
installation:
Connect up the unit and the KP14
Connect the cables to the J18 inputs on the Climatic
boards.
After a few minutes, the central unit should start its dialo-
gue. The LED on the Climatic board to the right of the J18
input should flash.
If this does not happen, check the wiring.
The only way to examine the problem in more detail is to
obtain a monitor and a mouse and contact the Lennox
services.
After installing a ClimaLook or ClimaLink central unit, it is vital to
perform the telephone communication tests.
Take a test telephone set and make sure you have a
connection.
Note the telephone number to which the central unit is
connected.
Connect the central unit and ask a person on the remote
site to test communication.
Obviously the central unit must be the only device installed
on the phone line. It cannot share the line with a fax or
another modem.
Reposition the keyboard in the task bar
by clicking on the minus sign in the
top right-hand part of the keyboard.
control interface CLIMALINK / CLIMALOOK
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...