Page 34 - IOM / ROOFTOP BALTIC Series - 0
8
03 - E
The actual resistance of ductwork systems is not always identical to the calculated theoretical values. To rectify this, it may
be necessary to modify the pulley and belt setting. To this effect, the motors are fitted with variable pulleys.
AIRFLOW BALANCING
Measure the absorbed amps
If the absorbed amps are greater than the rated values, the ventilation system has a lower pressure drop than anticipated.
Reduce the flow by reducing the rpm. If the system resistance is significantly lower than design, there is a risk that the motor
will overheat resulting in an emergency cut out.
If the absorbed amps are lower than the rated values, your system has a higher pressure drop than anticipated. Increase the
flow by increasing the rpm. At the same time you will increase the absorbed power which may result in having to increase
the motor size.
To carry out the adjustment and to avoid a time-consuming re-start, stop the machine and if necessary lock the main switch.
First unscrew the 4 Allen screw(s) on the pulley (see figure 35).
Min
Max
NB of turns
Pulley
Pulley
Dia /
Dia /
from fully
Actual diameter (DM) or distance between faces for a given
type
External
Min
Max
closed to
number of turns from fully closed with SPA belt in (mm)
Diameter Dist
Dist
fully open
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5,0
5,5
8450 /
120
95
116
5
113,9 111,8 109,7 107,6 105,5 103,4 101,3 99,2 97,1 95,0
-
D8450
20,2
28
5
21,0 21,8 22,5 23,3 24,1 24,9 25,7 26,4 27,2 28,0
-
8550 /
136
110
131
5
128,9 126,8 124,7 122,6 120,5 118,4 116,3 114,2 112,1 110,0
D8550
20,6
31,2
5
21,6 22,7 23,8 24,8 25,9 26,9 28,0 29,1 30,1 31,2
-
Table 1
VENTILaTION : PULLEYS
The easiest way to determine the fan rotation speed is to
use a tachometer. If not available the fan rpm can be
estimated using the following two methods.
1st Method with the pulley secured in place:
L
Measure the distance between the two outside faces of the
pulley.
Using table 1 the motor pulley actual diameter can be
estimated
ALLEN WRENCH 4
Fig. 35
Fig. 34
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...