IOM / ROOFTOP BALTIC Series -
08
03 - E Page 99
MAINTENANCE PLAN
TA
S
K
Check HP / LP safety switches
Check out
door fans and fan guards
Check position of all sensors
Check and clean if necessary all fresh air grilles
Check indoor and out
door coils, clean if
necessary
Check electric heater element for exces- sive corrosion
Check anti-vibration mountings, for wear and tear
.
Check refrigeration circuit for traces of acid in the oil
Check Glycol concentration in the HWC circuit
Check defrost cycle with 4-way valve inversion.
Gas burner module check for corrosion
Sweeping and cleaning the gas burner
Gas supply pressures / connections checks
Gas regulation valve settings
Check gas burner safety switches
OPERA
TING MODE
Inst
all manifold gauges on the circuit to be checked. Shut down
the axial fans and wait for the HP switch to shut down the compressor: 29bar (+1 / -0) auto-reset 22bar (+ - 0.7) Reconnect fans. Switch of
f the centrifugal supply fan and wait
for the LP switch to cut out: 0.5bar (+ - 0.5) reset 1.5bar (+-0.5).
Check the fan blades conditions and all fan guards and protec- tions
Check the good positioning and operation of all sensors of all sensors. Check the values given in the control system. Replace sensor if necessary
Check the fresh air grilles (if fitted). If dirty or damaged, remove them from unit and clean with high pressure water cleaner
. Refit
on unit once clean and dry
.
V
isually check the coils for dirt. If not too dirty
, cleaning with a
light brush may be enough (W
ARNING: Fins and copper tubes
are very fragile!
Any damage WILL
reduce the performances of
the unit). If very dirty
, deep industrial cleaning is required using
de-greasing agent
s.(External contractors must be called).
Isolate the unit; Pull the electric heater out of the heater module box and check the resist
ances fo traces of corrosion; Replace
resist
ance as required;
V
isually check anti-vibration mountings on compressors and
centrifugal fan. Replace if damaged.
Take a sample of oil from the refrigeration circuit.
Check the glycol concentration in the pressurised water circuit. ( a concentration of 30% gives a protection down to aprox. - 15°C) check the circuit pressure
Switch the unit to heat pump mode. Change the set point to obt
ain the st
andard defrost mode and reduce the cycle time to
the min value. Check the operation of the defrost cycle.
Pull out the burner to access the tubes (refer to Gas burner section in the IOM)
Clean the in-shot burners and the blower wheel lightly with a brush. Sweep the flue and flue box. Wipe-of
f the dust from the
housing of the motor
. Clean combustion air inlet louvers Pull-out
baf
fles from the tubes, sweep the tubes
CHECK FLUE BOX GASKET
refer to Gas burner section in the IOM for det
ails
refer to Gas burner section in the IOM for det
ails
refer to Gas burner section in the IOM for det
ails
6
YEARL
Y
E
S
T
IM
A
T
E
D
MONTHL
Y
QUARTERL
Y
M
O
N
T
H
LY
B
4
T
IM
E
WINTER
(mn)
15
0
5
0
5
0
5
0
1h if cleaning
0
1h if
replacement
0
1h if
replacement
∆
∆
30
∆
30
∆
30
∆
30
∆
15
∆
30
∆
30
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...