Page 68 - IOM / ROOF
T
O
P
BA
LTIC Series - 0
8
03 - E
control interf
aces ds50 menu tree
Main Screen Code
Description Code Description Code Description
Code UNIT
Min
Factory Max
5-Enable
3350
1-Fan On/Off 3351
(1)
On/Off
~
On
~
2-Fan Dead
3352
(1)
On/Off
~
On
~
3-F.Air
3353
(1)
On/Off
~
On
~
4-CO2
3354
(1)
On/Off
~
On
~
5-Comp.Cool. 3355
(1)
On/Off
~
On
~
6-Comp.Heat. 3356
(1)
On/Off
~
On
~
7-AuxHeat
3357
(1)
On/Off
~
On
~
8-Humidif.
3358
(1)
On/Off
~
On
~
9-Low Noise
3359
(1)
On/Off
~
Off
~
6-Capacity
3360
1-Room
3361 ~
1
4
100
2-Reheat
3362 ~
1
4
100
7-Safety
3370
1-Room Low
3371 °C 5
5
20
2-Room High 3372 °C 20 40
40
3-Sup.Lo.1
3373 °C 9 or 5
10 or 8 19
4-Sup.Lo.2
3374 °C 7 or 3
8 or 6
17
5-Sup.Lo.3
3375 °C 5 or 1
6 or 2
15
6-Sup.Hi.1
3376 °C 20 40
70
7-Sup.Hi.2
3377 °C 20 60
70
8-Room Low
3378 %
0
0
100
9-Room High 3379 %
0
100
100
4-Ventilation
3410
1-Air Flow
3411 Pa 0
25
1000
description
*[Enable] Stopping and running of the Fan Blower.[OFF] the
blower is stopped, [ON] the blower is running.
*[Enable] Stopping and running of the fan in the "Control
Dead Zone". [OFF] the blower is stopped, [ON] the blower is
running.
*[Enable] Run eco: [ON] the Economiser is running, [OFF]
the Economiser if stopped.
*[Enable] Run CO2 Sensor: [ON] Switch-on the CO2 on a
Zone, [OFF]Stop the CO2 sensor on a zone.
*[Enable] [OFF] Force the unloading of compressors in
cooling mode.
*[Enable] [OFF] Force the unloading of compressors in
heating mode.
*[Enable] [OFF] Force the unloading of heating module
(electric, gas or heat water coil)
*[Enable] [OFF] Force the unloading of humidity control.
*[Enable] Force the noise reduction mode. [ON] 50% of the
compressors are unloaded in "Unocupied" zone
*[Capacity Factor] Reactivity : Refer to "Climatic features" in
*IOM for details
*[Capacity Factor] Reactivity: Refer to "Climatic features" in
*IOM for details
*[Safety Limit] Room temperature "Low Limit" in °C Threshold
of activation of an alarm
*[Safety Limit] Room temperature "High Limit" in °C
Threshold of activation of an alarm
*[Safety Limit] Supply temperature low Limit (in °c) -
Threshold of activation of the 1° level of security: Reduce the
"Capacity Factor" by one stage of compressor and switch to
minimum Fresh Air,
*[Safety Limit] Supply temperature low Limit (in °c) -
Threshold of activation of the 2° level of security: Reduce the
"Capacity Factor" to zero and switch to 0% Fresh Air,open the
HWC valve.
*[Safety Limit] Supply temperature low Limit (in °c) -
Threshold of activation of the 3° level of security. - Alarm
threshold, the unit is switched off.
*[Safety Limit] Supply temperature high Limit (in °c) -
Threshold of activation of the 1° level of security: reduce the
capacity factor by one stage of compressor. Close the HWC
valve.
*[Safety Limit] Supply temperature high Limit (in °c) -
Threshold of activation of the 2° level of security: Alarm
threshold: Reduce the capacity factor to 0
*[Safety Limit] Room relative humidity low Limit (in %) -
Threshold of activation of the alarm
*[Safety Limit] Room humidity high Limit (in %) - Threshold of
activation of the alarm
*[Safety Limit] Airflow Detection Threshold of pressure
difference in Pa indicating Low Airflow Rate. If the pressure
difference across the filter is lower than this threshold the
safety is activated.
ALL
CODES SHOWING (1) CAN BE
ADJUSTED FOR EACH
TIME ZONE
Содержание Baltic BCK 020
Страница 1: ...BALTIC English August 2003 INSTALLATION OPERATING MAINTENANCE MANUAL ...
Страница 38: ...IOM ROOFTOP BALTIC Series 0803 E Page 37 VENTILaTION AIRFLOW BALANCING 020 025 Fig 37 ...
Страница 39: ...Page 38 IOM ROOFTOP BALTIC Series 0803 E VENTILaTION AIRFLOW BALANCING 035 030 Fig 38 ...
Страница 40: ...IOM ROOFTOP BALTIC Series 0803 E Page 39 VENTILaTION AIRFLOW BALANCING 045 050 040 Fig 39 ...
Страница 86: ...IOM ROOFTOP BALTIC Series 0803 E Page 85 CLIMATIC 50 CONTROLLER ELECTRICAL DATA wiring diagrams ...
Страница 87: ...Page 86 IOM ROOFTOP BALTIC Series 0803 E ELECTRICAL DATA wiring diagrams CLIMATIC 50 INPUT BCK BHK BGK BDK ...
Страница 101: ...Page 100 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 102: ...IOM ROOFTOP BALTIC Series 0803 E Page 101 EC declaration of conformity ...
Страница 103: ...Page 102 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 104: ...IOM ROOFTOP BALTIC Series 0803 E Page 103 EC declaration of conformity ...
Страница 105: ...Page 104 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...
Страница 106: ...IOM ROOFTOP BALTIC Series 0803 E Page 105 EC declaration of conformity ...
Страница 108: ...IOM ROOFTOP BALTIC Series 0803 E Page 107 EC declaration of conformity ...
Страница 109: ...Page 108 IOM ROOFTOP BALTIC Series 0803 E EC declaration of conformity ...