OMEGA
Installation Manual
Edition February
2020
Omega
platform lift
page 34 of 52
Contactor
feedback
20 (5.)
Ride to the next
stop position
The contacts of the ride contactors
(K50, K51) or the safety relay KSK
have not dropped off after completion
of a ride.
Approach from the stop position is no
longer possible unless the correct
signal (depending on the setting in
contactor feedback) is present.
Data exchange
between drive
and platform
board
21 (6.)
Ride is
interrupted
Communication via the rope did not
work.
Identified on the drive side.
WDTO occurred
drive
22 (7.)
Ride is
interrupted
Contact manufacturer!
(Watchdog timer timeout occurred)
SWR occurred
drive
23 (8.)
Ride is
interrupted
Contact manufacturer!
(Software reset occurred)
BOR occurred
drive
24 (9.)
Ride is
interrupted
This error occurs with a very short
power failure.
Internal FI error
25 (A.)
Ride is
interrupted
Indicates if an internal error has
occurred in the drive. Troubleshoot
the error in the FI error list according
to the FI display (Page 387).
FI overcurrent
26 (B.)
Ride is
interrupted
Overcurrent has occurred at the
drive. Check motor or check for short
circuit.
SPI timeout
platform
112 (-)
Ride is
interrupted
The communication between the PIC
microcontroller and the Echelon
Powerline module was faulty.
Powerline module defective.
Data exchange
between drive
and platform
board
113 (-)
Ride is
interrupted
Communication via the rope did not
work.
Platform sends data to the drive and
does not get a correct response.
Possible Cause: Failure of the
voltage regulator (24V) on the drive
board due to overheating.