OMEGA
Installation Manual
Edition February
2020
Omega
platform lift
page 25 of 52
Motor configuration
The drive unit control board supports 3 different ways to control the motor. The type of
control has to be defined in the menu.
The standard control used is type 3 with an inverter. In this case the frequencies for the
different driving speeds can be defined in this menu.
Menu item
Parameter
Meaning
Description
Control type
1
Main contactor
control
The contactors K1, K2 and K11 will
be controlled via the contact X4.
This control type works without a FI.
2
Inverter 1 out of n
The FI is controlled via the contacts
XRF, XAUF, XAB, XV1 and XV2.
The frequencies cannot be defined
in the menu but need to be adjusted
directly at the FI.
3
Inverter with
Modbus
The FI is controlled via serial data
network cable. The frequencies
have to be defined in the menu.
FI Model
1
Schneider Ativar
V12
Defines the inverter type used.
INFO: Is only possible when
choosing parameter 3 in the control
type menu item
2
Yaskawa V1000
FI Frequencies
Station run-in 10…25
Hz
Speed when driving in and out of a
stop position.
INFO: Is only possible when
choosing parameter 3 in the control
type menu item
Curves
10…50
Hz
Speed in curves or changes in
gradient.
INFO: Is only possible when
choosing parameter 3 in the control
type menu item
Drive
10…100
Hz
Speed on completely straight runs
INFO: Is only possible when
choosing parameter 3 in the control
type menu item.