OMEGA
Installation Manual
Edition February
2020
Omega
platform lift
page 29 of 52
If a point was actually saved it can be seen on the display. There the actual saved point
number and position count should be shown. The figure below shows the point 3, which
actually is the first point to be saved when driving out of the lower landing station.
If an intermediate landing station is saved then after the confirmation with the alarm button a
M will be shown beside the point number – see illustration below.:
If the platform is in the upper landing station and the last point was saved by pressing the
alarm button it is necessary to stop the teach-in process. This has to be done in the main
menu with the menu item: “teach-in stop”. If this item is confirmed with the downward
directional button the programming on the points is complete and the unit can be run down
to test the changing of the speeds in the saved points.
If there is a problem with the teach-in process and a point cannot be saved then one of the
following error messages will show on the display:
Display
Description
invalid interval
The platform always has to drive with curve speed (slow
speed) into a landing station. Otherwise this error will show.
point too close
The distance between 2 points is too close. It is important to
keep a minimum distance of 150mm between 2 points.
invalid teach in
At the end of the teach-in drive the relations of the saved
points are checked. If they are invalid this error will show.
rail too long
If this error is shown the total length of the rail is too long.
Please contact the supplier.
too many points
A maximum of 40 points can be saved. This number cannot
be exceeded.
Same or below p.
The same point has been programmed twice. Or a point has
been programmed below the last programmed point. Cause:
Wrong direction of rotation; Pulse generators do not work.
The point in the
intermediate landing
station was saved