8: Device Ports
SLB™ Branch Office Manager User Guide
132
2. Enter the following:
3. View or enter the following information for each outlet:
4. To save, click
Apply
.
Power Commands
to view CLI commands which correspond to the web page
entries described above.
Host Lists
A host list is a prioritized list of SSH, Telnet, and TCP hosts available for establishing incoming
modem connections or for the connect direct command on the CLI. The SLB branch office
manager cycles through the list until it successfully connects to one.
To view, update or delete a host list:
1. Click the
Devices
tab and select the
Host Lists
option. The following page displays:
Switching Delay
Number of milliseconds the SLB branch office manager between subsequent
switching. The range is 1000-2500 msec. The default is
2000 msec
(2 sec).
Over Current Alarm
If SNMP traps are enabled (see
Chapter 7: Services on page 84)
, a trap (alarm) is
sent if the total current for all outlets exceeds a threshold. Enter the number of
amps (measured in tenths of an amp) above which the SLB unit sends a trap. The
maximum is 180.
Note:
If the alarm goes off, a warning message displays on the CLI.
Current Level for all
Outlets
Displays the total load carried by the outlets.
Outlet
Displays the number of the outlet being configured.
Status
Displays the current state of the outlet.
Name
User-configurable name identifying the outlet.
Description (optional)
User-configurable text describing the outlet.
Current
Displays the load, in Amps, for the outlet.
Power State
Select whether the power should be on or off. Default is
Off
.
Wakeup Mode
Select whether, after a reboot, the power state for the outlet should be on, off, or
returned to the state it was in before the reboot. Default is
Off
.
Last State
Select whether to return the outlet to the state it was in before the reboot.
Reboot
To power cycle the outlet, select the checkbox. Default is unchecked.
Note:
You can reboot the SLB device on the
page, but after the reboot, the power outlet has the same power
state as it did before the reboot.
Содержание 100-120 VAC SLB
Страница 114: ...8 Device Ports SLB Branch Office Manager User Guide 114 Figure 8 4 Device Ports Settings ...
Страница 131: ...8 Device Ports SLB Branch Office Manager User Guide 131 Figure 8 10 Devices Power Outlets ...
Страница 174: ...9 USB Port SLB Branch Office Manager User Guide 174 Figure 9 3 Devices USB Modem ...
Страница 227: ...12 Maintenance SLB Branch Office Manager User Guide 227 Figure 12 1 Maintenance Firmware Configurations ...