Page 27
Buttons
61 Button „F-Off“
[S11] switches off humidity monitoring, e.g. to run dry the system (see page 31).
- Signal-LED „F-on“ (
52
) turns off.
Pressing the button for 5 seconds reactivates the humidity monitoring.
- Signal-LED „F-on“ (
52
) illuminates again.
62 Button „Reset maintenance“
[S10] must be pressed down for 5 seconds to reset the operating hour
meter to the default value of 400 hours.
This process is irreversible!
- Signal-LED „W“ (
58
) turns off, if it has been already activated.
63 Button „Test“ A Signal
[S9] may be pressed to check an optionally connected external signalisation.
- Relais „K-W“ activates and Relais „K-A“ deactivates.
- Signal LED „A“ (
59
)
illuminates
.
- Alarm „A“ must occur in the remote control center if a signal line is connected.
Fuses
A
Fuse „AC“
safeguards the AC circuit (supply voltage).
Type: 0,315 A, medium time lag
B
Fuse „DC“
safeguards the DC circuit (signal voltage).
Type: 2 A, medium time lag
Warning!
Pressing the button „F-off“ overrides the humidity monitoring.
The button must be used only, if a fault occurred, the „high pressure“ safety valve (18) is open
and the shut-off valve "cable pressure" (13) is shut.
Humidity monitoring must be reactivated immediatly after trouble-shooting, to assure proper
function of the pressurisation equipment.
Relay
with labeling acc. to wiring diagram
A
54
55
56
57
63
62
58
59
60
50
51
48
52 53
61
49
B 47
KY1
KY2
KK1
K-W
K-A
K-N
KY1
Содержание RTS 1000
Страница 15: ...Page 15 39 35 37 36 36 23 42 28 27 24 6 33 38 40 41 32 22 29 25 8...
Страница 21: ...Page 21...
Страница 47: ...Page 47 7 16 14 15 15 18 17 13 20 24 8 23 10 6 9 4 22 21 19 8...
Страница 51: ...Page 51 Pneumatics diagram Nr 074891 000...
Страница 53: ...Page 53 Circuit diagram Nr 074880 000...
Страница 55: ...Wiring diagram Nr 074881 000 Page 55...