Page 24
Service mode
System parameters of the MFR and the operating time counter of the ACS can be edited in the service mode.
WARNING!
These tasks must be accomplished by qualified personnel only.
The functionality of the pressurisation equipment may be damaged.
Menu selection:
Menu D1
>Display Settings
press soft key „select“
Display
D2.3
„Display Settings“ appears:
Pressing both soft keys (
45
) „up“ and „down“ at the same time activates the
service mode for 10 minutes.
The text „Service : active“ appears on the display above the line „Brightness”.
ACS settings
Menu selection:
Menu D2.3
>back
press soft key „select“
Menu D1
>Disp. Device : ACS
press soft key „select“
Menu D2.1
>ACS - Settings
press soft key „select“
Display
D3.2
„ACS - Settings“ appears.
The amount of total operating hours can be set here (e. g. after substitution of the ACS or a compressor).
Use soft keys (
45
) „up“ and „down“ to choose the value „Operating“.
Press soft key „select“.
Pressing the soft keys (
45
) „up“ and „down“ raise or lower the value.
Pressing the keys for a longer time increases the speed of alteration of the values of „runtime“, „maintenance“
and „operating hours“.
Pressing the soft key „set“ stores the set value.
MFR settings
Menu selection:
Menu D2.3
>back
press soft key „select“
Menu D1
>Disp. Device : MFR
press soft key „select“
Menu D2.2
>MFR - Settings
press soft key „select“
Display
D3.6
„MFR - Settings“ appears.
All values of the MFR set-up can be changed here (e. g. after substitution of system components).
Use soft keys (
45
) „up“ and „down“ to choose the value to change.
Press soft key „select“.
Pressing the soft keys (
45
) „up“ and „down“ raise or lower the value.
Pressing the keys for a longer time increases the speed of alteration of the values of „runtime“, „maintenance“
and „operating hours“.
If no runtime monitoring is required, set parameter „Runtime max.” to „0s”
Pressing the soft key „set“ stores the set value.
Display Settings
Brightness : 10
Timeout[min] : 30
>back
______________________
up
|
down
| select
ACS - Settings
>Set Top : Operating
flow max : 10000 l/h
Operating : 12345 h
back
______________________
up
|
down
| select
MFR - Settings
>Valve 1 : 60s
Valve 2 : 60s
Valve Pause : 0s
Valve F_up : 60s
______________________
up
|
down
| select
Содержание RTS 1000
Страница 15: ...Page 15 39 35 37 36 36 23 42 28 27 24 6 33 38 40 41 32 22 29 25 8...
Страница 21: ...Page 21...
Страница 47: ...Page 47 7 16 14 15 15 18 17 13 20 24 8 23 10 6 9 4 22 21 19 8...
Страница 51: ...Page 51 Pneumatics diagram Nr 074891 000...
Страница 53: ...Page 53 Circuit diagram Nr 074880 000...
Страница 55: ...Wiring diagram Nr 074881 000 Page 55...