Alert
Possible causes
Remedy
37)38)
Fluctuating DC link voltage
(1-4-1-1)
when
pump operates at rated values
Check mains voltage quality.
Mains fuse has tripped
Fit new mains fuse.
Brief interruption of mains voltage
Check the mains voltage.
24 V DC voltage supply overload
Reduce current input to 24 V DC, compare the
number of electrical connections with the
maximum permissible current load of the 24 V DC
Over Voltage
Line input voltage too high
Check the mains voltage.
Fluctuating DC link voltage
(1-4-1-1)
when
pump is not running
Check mains voltage quality.
Fluctuating DC link voltage
(1-4-1-1)
when
pump operates at rated values
Check mains voltage quality.
Mains fuse has tripped
Fit new mains fuse.
Braking resistor defective
Replace PumpDrive.
External voltage supplied to DigIn/AnIn
Wire properly and check wiring.
Ramp times too short
Select longer ramp times.
Pump runs in reverse when motor is not
supplied with current
Check swing check valve.
Operation with motor running idle
Restore load to motor.
Over Current
Mains power supply connected incorrectly
Connect mains power supply to L1, L2, L3, PE.
Motor terminal board wired incorrectly
(delta/star)
Wire motor terminal board correctly.
Incorrect motor data set
(3-3-2)
Match motor data settings to motor used.
Parallel operation of motors
This mode of operation is not permissible.
Sensor cable shielding connected incorrectly Connect sensor cable shielding to PE on one end
only.
PumpDrive rating < motor rating or
Output current < motor current
Wrong device ordered; mount larger PumpDrive
model.
Motor voltage too low
Change V/f characteristic to Linear (
Ramp times too short
Select longer ramp times.
Wrong direction of rotation of the pump
Change the direction of rotation of the motor via
the phase sequence.
Pump blocked mechanically/runs sluggishly
Check pump.
FI carrier frequency
(3-11-1-1)
set too high
Set carrier frequency to permissible range
(
Incorrect motor current measurement
(1-2-1-5)
Measure current using suitable snap-on ammeter
and compare with
(1-2-1-5)
.
Note: Approx. 10 % tolerance is permissible.
Pump runs in reverse when motor is not
supplied with current
Check swing check valve.
Over Current
Breakover Curre
Braking resistor
Stop ramp time too short
Increase ramp time.
Pump runs in reverse when motor is not
supplied with current
Check swing check valve.
Operation with motor running idle
Restore load to motor.
Generator operation of pump
Impermissible operating range
Int Temp incorr
Internal
temperature
impermissible
Ambient temperature of PumpDrive > 40 °C Impermissible operating range; mind power
Ambient temperature of PumpDrive < 0 °C
Dirt in external fans
Clean fans.
Heat sink/cooling fins dirty
Clean heat sink/cooling fins.
FI carrier frequency
(3-11-1-1)
set too high
Set carrier frequency to permissible range
(
PumpDrive rating < motor rating or
Output current < motor current
Wrong device ordered; mount larger PumpDrive
model.
37)
Disconnect PumpDrive from the power supply to rectify faults on current-carrying components. Observe the safety
information!
38)
Restore the PumpDrive default settings.