Table 18: Cable cross-sections of control terminals
Control terminal
Core cross-section
Maximum cable diameter
[mm]
Rigid and flexible cores
[mm
2
]
Flexible cores with wire end
sleeves
[mm
2
]
P4 terminal strip
0,2-1,5
0,75
9,5
30)
P7 terminal strip
0,2-2,5
0,25-1,5
GN D P 4
DI6
DI5
DI4
DI3
DI2
DI1
+24V
AGND
AN-OUT
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
SB1_GND
SB1
+
SB1
-
SB1_GND
SB1
+
SB1
-
SB1
Z-
SB1
Z+
ABNG P7
AIN1
GND
AIN2
+24V
NO2
COM2
NO1
COM1
10
9
3
1
2
4
5
6
7
8
P4
P7
P8
P5
P9
P6
Fig. 17: Control terminals
P4
P4 terminal strip
P5
Service interface: RS232
P6
LED traffic light function
P7
P7 terminal strip
P8
Field bus module connection panel
P9
Display connection
Table 19: Control terminal assignment, P4 terminal strip
Terminal strip
Terminal
Signal
Description
20
0V
Ground for +24 V
19
DIG IN6
Digital input (15/28 V DC)
18
DIB-IN5
Digital input (15/28 V DC)
17
DIG-IN4
Digital input (15/28 V DC)
30)
Impairment of protection provided by enclosure when cable diameters other than those specified are used.
5 Installation at Site
32 of 162
PumpDrive