G
N
D
D
I6
D
I5
D
I4
D
I3
D
I2
D
I1
+
2
4V
A
G
N
D
A
N
-O
U
T
G
N
D
D
I6
D
I5
D
I4
D
I3
D
I2
D
I1
+
2
4V
A
G
N
D
A
N
-O
U
T
G
N
D
D
I6
D
I5
D
I4
D
I3
D
I2
D
I1
+
2
4V
A
G
N
D
A
N
-O
U
T
10
9
8
7
6
5
4
3
2
1
10
9
8
7
6
5
4
3
2
1
10
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
20
19
18
17
16
15
14
13
12
11
20
19
18
17
16
15
14
13
12
11
20
S
B
1_
G
N
D
S
B
1+
S
B
1-
S
B
1_
G
N
D
S
B
1+
S
B
1-
S
B
1Z
-
S
B
1Z
+
Slave
Master
1
A
G
N
D
A
IN
1
G
N
D
A
IN
2
+
2
4V
N
O
2
C
O
M
2
N
O
1
C
O
M
1
10
9
3
1 2
4 5 6 7 8
A
G
N
D
A
IN
1
G
N
D
A
IN
2
+
2
4V
N
O
2
C
O
M
2
N
O
1
C
O
M
1
10
9
3
1 2
4 5 6 7 8
A
G
N
D
A
IN
1
G
N
D
A
IN
2
+
2
4V
N
O
2
C
O
M
2
N
O
1
C
O
M
1
10
9
3
1 2
4 5 6 7 8
Sensor
4...20mA
1
500Ω
Aux-Master
A
G
N
D
A
IN
1
G
N
D
A
IN
2
+
2
4V
N
O
2
C
O
M
2
N
O
1
C
O
M
1
10
9
3
1 2
4 5 6 7 8
S
B
1_
G
N
D
S
B
1+
S
B
1-
S
B
1_
G
N
D
S
B
1+
S
B
1-
S
B
1Z
-
S
B
1Z
+
S
B
1_
G
N
D
S
B
1+
S
B
1-
S
B
1_
G
N
D
S
B
1+
S
B
1-
S
B
1Z
-
S
B
1Z
+
Sensor
4...20mA
A
G
N
D
A
IN
1
G
N
D
A
IN
2
+
2
4V
N
O
2
C
O
M
2
N
O
1
C
O
M
1
10
9
3
1 2
4 5 6 7 8
Sensor
4...20mA
A
G
N
D
A
IN
1
G
N
D
A
IN
2
+
2
4V
N
O
2
C
O
M
2
N
O
1
C
O
M
1
10
9
3
1 2
4 5 6 7 8
P4
P4
P4
P4
P4
P4
P7
P7
P7
P7
P7
P7
Fig. 40: KSB local bus wiring for master/auxiliary master/slave mode (1 main pump, 1
auxiliary pump, 1 slave pump)
1.
The KSB local bus in the first and last PumpDrive must be terminated via a
resistor. This is implemented by means of a wire jumper between terminals 1
and 2 on terminal strip P4. If a graphical control panel is used on the first or last
PumpDrive, the wire jumper is not required.
2.
At the centre PumpDrives, the DIP switches on the rear must, if a graphical
control panel is used, be set to OFF to deactivate the terminating resistor of the
KSB local bus.
Master/AUX master/slave
mode
(1 main pump, 1 auxiliary
pump, 1 slave pump)
7 Commissioning/shutdown
70 of 162
PumpDrive