Terminal strip
Terminal
Signal
Description
GND P4
DI1
DI2
DI3
DI4
DI5
DI6
DI1
+24V
AGND
AN OUT
SB1--GND
SB1+
SB1--
SB1--GND
SB1+
SB1--
SB1Z--
SB1Z+
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
16
DIG-IN3
Digital input (15/28 V DC)
15
DIG-IN2
Digital input (15/28 V DC)
14
DIG-IN1
Digital input (15/28 V DC)
13
+24 V
+24 V DC voltage source, max. load 200 mA
12
0V-AN
Ground for AN-OUT
11
AN OUT
Analog output 0 - 10 V, max. load 5 mA
10
SB1-GND
Ground for KSB local bus
9
SB1 +
KSB local bus signal
8
SB1 -
KSB local bus signal
7
PE (EARTH)
Earth
6
PE (EARTH)
Earth
5
SB1-GND
Ground for KSB local bus
4
SB1 +
KSB local bus signal
3
SB1 -
KSB local bus signal
2
SB1Z-
Bus terminator for KSB local bus
1
SB1Z+
Bus terminator for KSB local bus
Terminal strip P4, terminals 13 to 20:
▪
PumpDrive is equipped with 6 digital inputs. Digital inputs 1 and 6 are factory-
defaulted.
▪
The functions of digital inputs 2 to 5 can be parameterised as required.
▪
Use terminal P4:13 (+24 V DC) to connect the inputs.
CAUTION
Differences in potential
Damage to PumpDrive!
▷
Never connect an ex24 V DC voltage source to a digital input.
Terminal strip P4, terminals 11 and 12:
▪
PumpDrive is equipped with an analog output whose output value can be
parameterised via the control panel.
▪
Analog signals to a higher-level control station must be electrically isolated when
they are transmitted, for example by using isolating amplifiers.
Table 20: Control terminal assignment, P7 terminal strip
Terminal strip
Terminal
Signal
Description
AIN1
AGND P7
GND
AIN2
NO2
COM2
NO1
COM1
+24V
10
9
8
7
6
5
4
3
2
1
10
0V-AN
Ground for AIN 1/2
31)
9
AN1-IN
Programmable analog input 1
32)
8
PE (EARTH)
Earth
7
0V
Ground for +24 V
6
AN2-IN
Programmable analog input 2, factory setting:
Actual value source 4 - 20 mA
5
+24 V
+24 V DC voltage source, max. load 200 mA
4
NO2
NO contact, "NO" No. 2 (250 V AC, 1 A)
3
COM2
NO contact, "NO" No. 2 (250 V AC, 1 A)
2
NO1
NO contact, "NO" No. 1 (250 V AC, 1 A)
1
COM1
NO contact, "COM" No. 1 (250 V AC, 1 A)
Digital inputs
Analog outputs
31)
The ground at terminal P7:7 can also be used to connect an analog ground. AGND and GNG have the same potential.
32)
Analog signals from a higher-level control station must be electrically isolated when they are transmitted to PumpDrive,
for example by using isolating amplifiers.
5 Installation at Site
PumpDrive
33 of 162