Parameter Description
Factory
setting
Setting
Unit
Access level
Possible settings
EP
MP
Min.
Max.
3-12-5-1
Max Pps Run
Specification of
maximum number
of running pumps
1
1
1
6
Customer
3-12-5-2
No of Standby
Specification of
number of stand-by
pumps
0
0
0
6
Factory
3-12-5-3
Tm Cons Add Pum
Time constant
before starting the
next pump
10
10
3
500
s
Customer
3-12-5-4
Tm Stop Pump
Time constant
before stopping the
next pump
20
20
10
500
s
Customer
3-12-5-5
Enable Pps Chg
Activate/deactivate
24 h pump
changeover cycle
2
2
Customer Disabled
Enabled
3-13
LON Module
LON module
3-14
Profibus Module
Profibus module
4
Information
Main menu information
4-1
PDrive Info
Menu for displaying PumpDrive information
4-1-1
PDrive ID
Submenu for
displaying
PumpDrive ID
4-1-1-1
Device Ser No
Serial number of
device
0
0
All
4-1-1-2
SW Version
Software version
0
0
All
4-1-1-3
Device Type
Device type
0
0
All
4-1-1-4
Dev Type Code
Code of device type
0
0
0
0
All
4-1-1-5
Bin File Vers
Version of binary
file
0
0
0
0
Service
4-1-1-6
Prog Lang 1
Freely
programmable
language 1
0
0
Customer
4-1-1-7
Prog Lang 2
Freely
programmable
language 2
0
0
Customer
4-1-1-8
Bin File Chksum
Checksum of binary
file
0
0
0
65535
Service
4-1-1-9
Bin File Length
Size
of binary file
0
0
0
65535
Service
4-2
Panel
Menu for control panel
4-2-1
Panel Ident
Submenu
10 Parameter lists
128 of 162