MULTICAL®
603
Kamstrup
A/S
∙
Technical
description
∙
5512
‐
2029_A1_GB_06.2017
89
603
‐
E/F
Application
no.
7
Open
system
with
2
flow
sensors
Forward
energy:
E4
=
V1
(t1
‐
t3)k
t1:Inlet
Return
energy:
E5
=
V2
(t2
‐
t3)k
t2:Inlet
Δ
E
=
E4
‐
E5
can
be
calculated
by
the
meter.
Heat
energy:
E2
=
V2
(t1
‐
t2)k
t2:Outlet
t3
is
measured
or
programmed
Mass:
M1
=
V1
(Kmass
t1)
Mass:
M2
=
V2
(Kmass
t2)
Config
A
=
3
(inlet)
or
4
(outlet)
(no
influence
on
E2,
E4
or
E5)
603
‐
E/F
Application
no.
8
Hot
‐
water
boiler
with
circulation
Total
consumption
E1
=
V1
(t1
‐
t2)k
t2:Outlet
Circulated
consumption:
E7
=
V2
(t1
‐
t3)k
t3:Outlet
LV: Hot domestic water
LVK: Heat circulation
KV: Cold water
Config.
A
=
4
(outlet)
* M2 = V2 (Kmass t3). V2 is mass‐adjusted with t3 when selecting special DDD‐code.