MULTICAL®
603
Kamstrup
A/S
∙
Technical
description
∙
5512
‐
2029_A1_GB_06.2017
23
3.2.3
Flow
sensor
coding
>CCC<
The
CCC
‐
code
optimises
the
display
resolution
for
the
selected
flow
sensor
size,
and
at
the
same
time
the
type
approval
regulations
as
to
minimum
resolution
and
maximum
register
overflow
are
observed.
Below,
the
possible
display
resolutions
with
MULTICAL®
603
according
to
the
type
approval
rules
are
shown.
Number
of
decimals
in
display
Energy
Volume
/
Mass
Flow
/
Power
qp
[m
3
/h]
7/8
digits
kWh
1
MWh
Gcal
GJ
m
3
tons
l/h
m
3
/h
kW
MW
0.6
≤
1.5
7
1
4
3
3
0
‐
1
‐
0.6
≤
15
7
0
3
2
2
0
‐
1
‐
8
1
4
3
3
‐
4
≤
150
7
‐
2
1
1
‐
2
0
‐
8
0
3
2
2
‐
40
≤
1500
7
‐
1
0
0
‐
1
‐
2
8
‐
2
1
1
400
≤
15000
7
‐
‐
‐
‐
‐
‐
‐
‐
8
‐
1
0
0
0
1
The
CCC
codes
for
MULTICAL®
603
are
grouped
according
to
the
type
of
connected
flow
sensor.
Nine
groups
have
been
created,
which
are
all
tied
to
a
connection
type.
The
connection
type
is
selected
as
part
of
the
meter’s
type
number.
CCC
Flow
sensor
type
Pulse
frequency
Bounce
dampin
g
Pulses
+
Data
Auto
Detect
7/8
digits
Connection
type
Pulse
time
Direct
Opto
ON
(LO)
OFF
(HI)
0XX
Mechanical
meters
delivering
slow
pulses
with
bounce
<
1
Hz
Yes
P
No
7/8
L
‐
>300
ms
>10
ms
1XX
Electronic
meters
with
quick
and
bounce
‐
free
pulses
<
128
Hz
No
P
7
C
‐
7
‐
8
1
P
>1
ms
>4
ms
2XX
8
C
4XX
Electronic
meters
with
quick
and
bounce
‐
free
pulses
as
well
as
data
for
info
codes
for
ULTRAFLOW®
X4
P+D
7
1
‐
2
‐
7
‐
8
1
‐
5XX
8
8XX
Electronic
meters
with
quick
and
bounce
‐
free
pulses
as
well
as
data
for
info
codes
for
ULTRAFLOW®
X4
and
self
‐
configuration
Yes
7/8
9XX
Electronic
meters
with
slow
and
bounce
‐
free
pulses
<
8
Hz
P
No
J
>30
ms
>100
ms
1
Connection type 1‐2 means connection of 1 or 2 provided ULTRAFLOW®, 7‐8 means prepared for 1 or 2 ULTRAFLOW®.