MULTICAL®
603
86
Kamstrup
A/S
∙
Technical
description
∙
5512
‐
2029_A1_GB_06.2017
Energy
types
E1…E7
are
described
by
application
examples
below.
603
‐
A/B/C/D/E/F/G
Application
no.
1
Closed
thermal
system
with
1
flow
sensor
Heat
energy:
E1
=
V1(t1
‐
t2)k
t1:inlet
or
t2:outlet
Cooling
energy:
E3
=
V1
(t2
‐
t1)k
t2:inlet
or
t1:outlet
Flow
sensor
V1
is
mounted
in
inlet
or
outlet
as
selected
during
configuration.
Mass:
M1
=
V1
(Kmass
t1)
or
Mass:
M1
=
V1
(Kmass
t2)
depending
on
inlet/outlet
programming.
Config
A
=
3
(inlet)
or
4
(outlet)
603
‐
E/F
Application
no.
2
Closed
thermal
system
with
2
identical
flow
sensors
Leakage
monitoring
Permanent
operational
monitoring
Billing
energy:
E1
=
V1(t1
‐
t2)k
t1:Inlet
Control
energy:
E2
=
V2
(t1
‐
t2)k
t2:Outlet
t3
can
be
used
for
check
measurement
of
either
the
inlet
or
outlet
temperature,
but
t3
is
not
used
for
the
energy
calculation.
Mass:
M1
=
V1
(Kmass
t1)
Mass:
M2
=
V2
(Kmass
t2)
Config.
A
=
3
(Inlet)