MULTICAL®
603
84
Kamstrup
A/S
∙
Technical
description
∙
5512
‐
2029_A1_GB_06.2017
Normal
resolution
Resolution
level
MWh
Gcal
kWh
GJ
m
3
tons
3
0.0001
0.1
0.001
0.001
2
0.001
1
0.01
0.01
1
0.01
‐
0.1
0.1
0
0.1
‐
1
1
Table 1, Normal resolution
Flow sensor size
High
resolution
qp ≤ 1.5
0.001 kWh
0.01 litre
1.5 < qp ≤ 15
0.01 kWh
0.1 litre
15 < qp ≤ 150
0.1 kWh
1 litre
150 < qp ≤ 1500
1 kWh
0.01 m
3
1500 < qp ≤ 15000
0.01 MWh
0.1 m
3
Table 2, High resolution
Energy
Volume
Normal
resolution
High
resolution
Table 3
,
Examples of normal and high resolution
While
the
meter
is
in
TEST
mode,
all
integrations
are
carried
out
at
an
interval
of
2
seconds,
irrespective
of
the
chosen
L
‐
code.
The
above
high
resolution
registers
can
also
be
seen
in
the
TECH
loop,
see
paragraph
6.2.
However,
here
the
integration
interval
will
follow
the
meter’s
usual
interval,
defined
by
the
L
‐
code.
While
the
meter
is
in
TEST
mode,
high
‐
resolution
pulses
can
be
generated
for
test
purposes
via
Pulse
interface
(see
paragraph
13).