14.
Temperature
sensor
offset
(t
r0
)
Temperature
sensor
offset
(t
r0
)
can
be
adjusted
in
the
SETUP
loop.
Depending
on
the
meter’s
configuration,
this
function
can
be
disabled
and
the
menu
item
will
in
that
case
display
“Off”.
Offset
can
be
adjusted
in
the
interval
‐
0.99…0.99
K.
By
pressing
the
primary
key,
the
0
and
the
sign
start
flashing,
and
it
is
now
possible
to
toggle
between
–
and
+,
indicated
in
the
display
by
the
fact
that
the
minus
sign
flashes
and
switches
off
respectively.
By
pressing
the
arrow
keys,
the
meter
shifts
focus
to
the
first
decimal,
i.e.
it
is
not
possible
to
change
the
value
of
the
first
digit
as
the
valid
interval
is
‐
0.99…0.99
K.
Both
the
first
and
second
decimal
can
be
set
to
a
value
between
0
and
9.
Read
more
about
order
data
in
paragraph
7.3.
Note:
The
set
offset
is
active
for
all
temperature
sensors
that
are
connected
to
MULTICAL®
603,
i.e.
both
t1,
t2
and
t3.
15.
Radio
on/off
The
meter’s
radio/wireless
communication
can
be
adjusted
to
being
switched
on
or
switched
off.
The
meter
automatically
turns
on
the
radio
when
the
meter
leaves
the
transport
state,
i.e.
when
the
meter
has
registered
a
flow
of
1
%
of
q
p
or
larger.
The
radio
on/off
function
in
the
SETUP
loop
is
primarily
used
for
switching
on
the
radio
in
transport
state,
without
the
meter
having
registered
flow,
as
well
as
for
switching
off
the
radio
when
the
meter
is
dismounted
after
having
been
in
operation,
e.g.
If
the
meter
is
to
be
sent
by
airfreight.
The
meter’s
present
condition
is
indicated
by
two
symbols
in
the
bottom
left
corner
of
the
display.
The
above
definition
of
the
radio
on/off
symbols
simplify
the
use
of
radio
on/off
in
the
SETUP
loop
too
as
it
is
possible
to
switch
between
radio
on/off
whether
a
module
is
mounted
in
the
meter
or
not.
This
provides
flexibility
as
the
utility
can
configure
the
meter
prior
to
mounting
a
module
and
thus
ensure
that
radio
by
default
is
either
switched
on
or
switched
off
when
the
module
is
subsequently
mounted.
Be
aware
of
setting
the
required
offset
adjustment,
not
the
error
of
the
temperature
sensor
pair.
If
the
selected
temperature
sensor
pair
contributes
with
an
error
of
‐
0.20
K,
the
meter’s
offset
must
be
set
at
0.20
K.
IMPORTANT:
‐
If
the
meter's
radio
communication
is
switched
off
via
the
SETUP
loop,
the
meter
will
subsequently
switch
on
the
radio
communication
again
when
a
flow
of
1
%
of
qp
or
larger
has
been
registered
for
the
first
time.
‐
The
symbols
for
radio
on/off
indicate
whether
the
meter
allows
radio
communication,
not
whether
a
radio
module
has
activated
its
radio
communication.
Please
be
aware
of
this
when
troubleshooting
the
meter’s
wireless
communication.