Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
35
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
EtherNet Bus
P12.3.3.6
MSTP Fault Code
600
0 = None
1 = Sole Master
2 = Duplicate MAC ID
3 = Baud rate fault
P12.3.3.7
2
MSTP Fault Response
0
2526
See Par ID 2516
P12.3.3.8
1
MSTP Max Master
127
1537
Table 42. SA Bus—P12.3.4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P12.3.4.1
12
SA Bus Baud Rate
2
1727
See Par ID 584
P12.3.4.2
12
SA Bus Device Address
204
254
204
1726
P12.3.4.3
12
SA Bus Instance Number
0
4194302
0
1728
P12.3.4.4
2
SA Bus Comm Timeout
0
60000
10000
1730
P12.3.4.5
SA Bus Protocol Status
1731
See Par ID 599
P12.3.4.6
2
SA Bus Fault Response
0
1732
See Par ID 2516
Table 41. BACnet MS/TP—P12.3.3, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
Table 43. Basic Setting—P12.4.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P12.4.1.1
1
IP Address Mode
1
1500
0 = Static IP
1 = DHCP with AutoIP
P12.4.1.2
Active IP Address
1507
P12.4.1.3
Active Subnet Mask
1509
P12.4.1.4
Active Default Gateway
1511
P12.4.1.5
MAC Address
1513
P12.4.1.6
1
Static IP Address
192.168.1.254
1501
P12.4.1.7
1
Static Subnet Mask
255.255.255.0
1503
P12.4.1.8
1
Static Default Gateway
192.168.1.1
1505
P12.4.1.9
1
Enable BACnetIP
0
1725
See Par ID 1679
Table 44. Modbus TCP—P12.4.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P12.4.2.1
Connection Limit
5
609
P12.4.2.2
Modbus TCP Unit ID
1
610
P12.4.2.3
Comm Timeout Modbus TCP 0
60000
ms
10000
611
P12.4.2.4
Modbus TCP Protocol Status
612
See Par ID 599
P12.4.2.5
Modbus TCP Fault Response
0
2517
See Par ID 2516