Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
25
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Drive Control
Table 26. Basic Setting—P4.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.1.1
2
Keypad Reference
See Par ID 101
See Par ID 102
Hz
0.00
141
P4.1.2
2
Keypad Direction
0
116
0 = Forward
1 = Reverse
P4.1.3
2
Keypad Stop
1
114
0 = Enabled-Keypad Operation
1 = Always Enabled
P4.1.4
2
Hand Key Enable
0
1724
0 = Enabled
1 = Disabled
P4.1.5
1
Reverse Enable
0
1679
0 = Disabled
1 = Enabled
P4.1.6
Change PhaseSequence
Motor
0
2515
0 = Change Disable
1 = Change Enable
P4.1.7
2
Power Up HOA Select
0
1685
0 = Hold Last
1 = Hand Control
2 = Auto control
3 = Off
P4.1.9
2
Run Delay Time
0
32500
s
0
2423
P4.1.10
2
Start Mode
0
252
0 = Ramp
1 = Flying Start
P4.1.11
2
Stop Mode
0
253
0 = Coasting
1 = Ramp
P4.1.12
2
Ramp 1 Shape
0.0
10.0
s
0.0
247
P4.1.13
2
Ramp 2 Shape
0.0
10.0
s
0.0
248
P4.1.14
2
Accel Time 2
0.1
3000.0
s
10.0
249
P4.1.15
2
Decel Time 2
0.1
3000.0
s
10.0
250
P4.1.16
2
Power Loss Function
0
267
See Par ID 1679
P4.1.17
2
Power Loss Time
0.3
5.0
s
2.0
268
P4.1.18
1
2
2nd Stage Ramp Frequency See Par ID 101
See Par ID 102
Hz
30.00
2444
Table 27. Brake—P4.2
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.2.1
1
2
DC-Brake Current
DriveNomCurr
CT*15/100
DriveNomCurr
CT*15/10
A
DriveNomCurr
CT*1/2
254
P4.2.2
1
2
Start DC-Brake Time
0.00
600.00
s
0.00
263
P4.2.3
1
2
Stop DC-Brake Frequency
0.10
10.00
Hz
1.50
262
P4.2.4
1
2
Stop DC-Brake Time
0.00
600.00
s
0.00
255
P4.2.5
1
2
Brake Chopper Define
0
251
0 = Disabled
1 = B(Run) T(Rdy)
2 = External
3 = B(Rdy) T(Rdy)
4 = B(Run) T(No)
P4.2.6
1
2
Flux Brake
0
266
0 = Off
1 = On
P4.2.7
1
2
Flux Brake Current
ActiveMotor
NomCurr*1/10
See Par ID 107
A
ActiveMotorNom
Curr*1/2
265