Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
17
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Parameters
Table 16. Operate Mode—O
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
O1
Output Frequency
Hz
0
1
O2
Freq Reference
Hz
0
24
O3
Motor Speed
rpm
0
2
O4
Motor Current
A
0
3
O5
Motor Torque
%
0
4
O6
Motor Power
%
0
5
O7
Motor Voltage
V
0
6
O8
DC-link Voltage
V
0
7
O9
Unit Temperature
°C
0
8
O10
Motor Temperature
%
0
9
R11
2
Keypad Reference
PAR ID 101
PAR ID 102
Hz
0
141
Table 17. Basic Parameters—P1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P1.1
12
Min Frequency
0.00
See Par ID 102
Hz
0.00
101
P1.2
12
Max Frequency
See Par ID 101
400.00
Hz
Varies
102
P1.3
2
Accel Time 1
0.1
3000.0
s
20.0
103
P1.4
2
Decel Time 1
0.1
3000.0
s
20.0
104
P1.5
1
Motor Nom Current
DriveNomCurr
CT*1/10
DriveNomCurr
CT*2
A
DriveNomCurrCT
486
P1.6
1
Motor Nom Speed
300
20000
rpm
Varies
489
P1.7
1
Motor PF
0.30
1.00
0.85
490
P1.8
1
Motor Nom Voltage
180
690
V
Varies
487
P1.9
1
Motor Nom Frequency
8.00
400.00
Hz
Varies
488
P1.10
12
HOA Source
0
2465
0 = I/O Terminal/Keypad/Fieldbus
1 = Keypad
2 = IO Terminal
3 = Fieldbus
P1.11
2
Hand Control Place
0
1695
0 = Keypad
1 = I/O Terminal Start 1
2 = I/O Terminal Start 2
3 = Fieldbus