Step 5—Standard Parameter List
24
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 24. Analog Output 1—P3.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P3.3.1
2
AO1 Mode
0
227
See Par ID 222
P3.3.2
2
AO1 Function
1
146
0 = Not Used
1 = Output Frequency
2 = Freq Reference
3 = Motor Speed (0–Nom)
4 = Motor Current (0–Nom)
5 = Motor Torque (0–Nom)
6 = Motor Power (0–Nom)
7 = Motor Voltage (0–Nom)
8 = DC-Bus Voltage
19 = AI1
20 = AI2
21 = Output Freq (-2-+2N)
22 = Motor Torque (-2-+2N)
23 = Motor Power (-2-+2N)
24 = PT100 Temperature
33 = SlotA PT100 Temp Channel 1
34 = SlotA PT100 Temp Channel 2
35 = SlotA PT100 Temp Channel 3
36 = SlotB PT100 Temp Channel 1
37 = SlotB PT100 Temp Channel 2
38 = SlotB PT100 Temp Channel 3
39 = User Defined Output
40 = Motor Current (-2-+2N)
P3.3.3
2
AO1 Minimum
1
149
0 = 0 V / 0 mA
1 = 2 V / 4 mA
P3.3.4
2
AO1 Filter Time
0.00
10.00
s
1.00
147
P3.3.5
2
AO1 Scale
10
1000
%
100
150
P3.3.6
2
AO1 Inversion
0
148
See Par ID 181
P3.3.7
2
AO1 Offset
-100.00
100.00
%
0.00
173
Table 25. Analog Output 2—P3.4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P3.4.1
2
AO2 Mode
0
228
See Par ID 222
P3.4.2
2
AO2 Function
4
229
See Par ID 146
P3.4.3
2
AO2 Minimum
1
232
See Par ID 149
P3.4.4
2
AO2 Filter Time
0.00
10.00
s
1.00
230
P3.4.5
2
AO2 Scale
10
1000
%
100
233
P3.4.6
2
AO2 Inversion
0
231
See Par ID 181
P3.4.7
2
AO2 Offset
-100.00
100.00
%
0.00
234