Step 5—Standard Parameter List
20
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
P2.2.13
23
Ext. Fault 2 NC
1
2294
See Par ID 190
P2.2.14
2
Ext. Fault 2 Text
1
2298
See Par ID 2297
P2.2.15
23
Ext. Fault 3 NO
0
2295
See Par ID 190
P2.2.16
23
Ext. Fault 3 NC
1
2296
See Par ID 190
P2.2.17
2
Ext. Fault 3 Text
2
2299
See Par ID 2297
P2.2.18
24
Fault Reset
5
200
See Par ID 190
P2.2.19
23
Run Enable
1
194
See Par ID 190
P2.2.20
23
Preset Speed B0
6
205
See Par ID 190
P2.2.21
23
Preset Speed B1
0
206
See Par ID 190
P2.2.22
23
Preset Speed B2
0
207
See Par ID 190
P2.2.23
23
Jog Enable
0
199
See Par ID 190
P2.2.24
23
Accel/Decel Time Set
0
195
See Par ID 190
P2.2.25
23
Accel/Decel Prohibit
0
201
See Par ID 190
P2.2.26
24
No Access To Param
0
215
See Par ID 190
P2.2.27
23
Auto Control
9
196
See Par ID 190
P2.2.28
23
Hand Control
0
197
See Par ID 190
P2.2.29
23
Auto 1/2 Select
0
209
See Par ID 190
P2.2.30
23
HOA On/Off
1
2395
See Par ID 190
P2.2.32
24
Parameter Set1/2 Sel
0
2312
See Par ID 190
P2.2.33
23
AI Ref Source Select
0
208
See Par ID 190
P2.2.34
24
Bypass Start
8
218
See Par ID 190
P2.2.35
23
Bypass Overload
0
1246
See Par ID 190
P2.2.40
23
DC Brake Active
0
202
See Par ID 190
P2.2.42
23
Fire Mode
7
220
See Par ID 190
P2.2.43
23
Fire Mode Ref 1/2 Select
0
221
See Par ID 190
P2.2.44
23
Fire Mode Reverse
0
2119
See Par ID 190
Table 19. Preset Speed—P2.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P2.3.1
2
Preset Speed 1
0.00
See Par ID 102
Hz
5.00
105
P2.3.2
2
Preset Speed 2
0.00
See Par ID 102
Hz
10.00
106
P2.3.3
2
Preset Speed 3
0.00
See Par ID 102
Hz
15.00
118
P2.3.4
2
Preset Speed 4
0.00
See Par ID 102
Hz
20.00
119
P2.3.5
2
Preset Speed 5
0.00
See Par ID 102
Hz
25.00
120
P2.3.6
2
Preset Speed 6
0.00
See Par ID 102
Hz
30.00
121
P2.3.7
2
Preset Speed 7
0.00
See Par ID 102
Hz
35.00
122
P2.3.8
2
Jog Reference
See Par ID 101
See Par ID 102
Hz
0.00
117
Table 18. Digital Input—P2.2, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note