Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
21
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 20. AI1 Settings—P2.4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P2.4.1
AI1 Mode
1
222
0 = 0–20 mA
1 = 0–10 V
P2.4.2
2
AI1 Signal Range
0
175
0 = 0–100%/0–20 mA/0–10 V
1 = 20–100%/4–20 mA/2–10 V
2 = Customized
P2.4.3
2
AI1 Custom Min
0.00
See Par ID 177
%
0.00
176
P2.4.4
2
AI1 Custom Max
See Par ID 176
100.00
%
100.00
177
P2.4.5
2
AI1 Filter Time
0.00
10.00
s
0.10
174
P2.4.6
2
AI1 Signal Invert
0
181
0 = Not Inverted
1 = Inverted
Table 21. AI2 Settings—P2.5
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P2.5.1
AI2 Mode
0
223
0 = 0–20 mA
1 = 0–10 V
2 = -10– +10 V
P2.5.2
2
AI2 Signal Range
1
183
0 = 0–100%/0–20 mA/
0 =
0–10 V/-10–10 V
1 = 20–100%/4–20 mA/
1 =
2–10 V/-6–10 V
2 = Customized
P2.5.3
2
AI2 Custom Min
0.00
See Par ID 185
%
0.00
184
P2.5.4
2
AI2 Custom Max
See Par ID 184
100.00
%
100.00
185
P2.5.5
2
AI2 Filter Time
0.00
10.00
s
0.10
182
P2.5.6
2
AI2 Signal Invert
0
189
See Par ID 181
Table 22. Digital Output—P3.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P3.1.1
2
DO1 Function
1
151
0 = Not Used
1 = Ready
2 = Run
3 = Fault
4 = Fault Invert
5 = Warning
6 = Reversed
7 = At Speed
8 = Zero Frequency
9 = Freq Limit 1 Superv
10 = Freq Limit 2 Superv
13 = OverHeat Fault
14 = OverCurrent Regular
15 = OverVoltage Regular
16 = UnderVoltage Regular
17 = 4mA Ref Fault/Warning
20 = Torq Limit Superv
21 = Ref Limit Superv
22 = Control from I/O
23 = Un-Requested Rotation
23 =
Direction
24 = Thermistor Fault Output