Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
27
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Protections
P5.1.10
2
Switching Frequency
MinSwitchFreq MaxSwitchFreq kHz
DefaultSwitch
FreqCT
2522
P5.1.11
2
Sine Filter Enable
0
1665
See Par ID 1679
P5.1.12
1
2
OverVoltage Control
1
294
See Par ID 1679
Table 30. Basic Setting—P5.1, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
Table 31. Motor—P6.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P6.1.1
1
2
Output Phase Fault
2
308
0 = No Action
1 = Warning
2 = Fault
3 = Fault, Coast
P6.1.2
1
2
Ground Fault
2
309
See Par ID 308
P6.1.3
2
Ground Fault Limit
0
30
%
15
2158
P6.1.4
1
2
Motor Thermal Protection
2
310
See Par ID 308
P6.1.5
2
Motor Thermal F0 Current
0.0
150.0
%
40.0
311
P6.1.6
2
Motor Thermal Time
1
200
min
12
312
P6.1.7
1
2
Stall Protection
0
313
See Par ID 308
P6.1.8
2
Stall Current Limit
0.1
ActiveMotor
NomCurr*2
A
ActiveMotorNom
Curr*13/10
314
P6.1.9
2
Stall Time Limit
1.0
120.0
s
15.0
315
P6.1.10
2
Stall Frequency Limit
1.00
See Par ID 102
Hz
25.00
316
P6.1.11
1
2
Underload Protection
0
317
See Par ID 308
P6.1.12
2
Underload Fnom Torque
10.0
150.0
%
50.0
318
P6.1.13
2
Underload F0 Torque
5.0
150.0
%
10.0
319
P6.1.14
2
Underload Time Limit
2.00
600.00
s
20.00
320
P6.1.15
1
2
Thermistor Fault Response
2
333
See Par ID 308
P6.1.16
1
2
PT100 Fault Response
2
337
See Par ID 308
P6.1.17
2
Preheat Mode
0
2159
See Par ID 1679