Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
23
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
P3.2.8
2
Torque Limit Supv Val
-1000.0
1000.0
%
100.0
160
P3.2.9
2
Torque Limit Supv Hyst
1.0
5.0
%
1.0
2202
P3.2.10
2
Ref Limit Supv
0
161
See Par ID 154
P3.2.11
2
Ref Limit Supv Val
0.00
See Par ID 102
Hz
0.00
162
P3.2.12
2
Ref Limit Supv Hyst
0.10
1.00
Hz
0.10
2203
P3.2.13
2
Temp Limit Supv
0
165
See Par ID 154
P3.2.14
2
Temp Limit Supv Val
-10.0
75.0
°C
40.0
166
P3.2.15
2
Temp Limit Supv Hyst
1.0
10.0
°C
1.0
2204
P3.2.16
2
Power Limit Supv
0
167
See Par ID 154
P3.2.17
2
Power Limit Supv Val
-200.0
200.0
%
0.0
168
P3.2.18
2
Power Limit Supv Hyst
0.1
10.0
%
0.1
2205
P3.2.19
2
AI Supv Select
0
170
0 = AI1
1 = AI2
P3.2.20
2
AI Limit Supv
0
171
See Par ID 154
P3.2.21
2
AI Limit Supv Val
0.00
100.00
%
0.00
172
P3.2.22
2
AI Supv Hyst
1.00
10.00
%
1.00
2198
P3.2.23
2
Motor Current 1 Supv
0
2189
See Par ID 154
P3.2.24
2
Motor Current 1 Supv Value 0.0
DriveNomCurr
CT*2
A
DriveNomCurrCT
2190
P3.2.25
2
Motor Current 1 Supv Hyst
0.1
1.0
A
0.1
2196
P3.2.26
2
Motor Current 2 Supv
0
2191
See Par ID 154
P3.2.27
2
Motor Current 2 Supv Value 0.0
DriveNomCurr
CT*2
A
DriveNomCurrCT
2192
P3.2.28
2
Motor Current 2 Supv Hyst
0.1
1.0
A
0.1
2197
P3.2.29
2
Second AI Supv Select
0
2193
See Par ID 170
P3.2.30
2
Second AI Limit Supv
0
2194
See Par ID 154
P3.2.31
2
Second AI Limit Supv Val
0.00
100.00
%
0.00
2195
P3.2.32
2
Second AI Supv Hyst
1.00
10.00
%
1.00
2199
Table 23. Supervisions—P3.2, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note