Step 5—Standard Parameter List
26
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Motor Control
Table 28. Skip Frequency—P4.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.3.1
2
Skip Range Ramp Factor
0.1
10.0
1.0
264
P4.3.2
2
Skip F1 Low Limit
0.00
See Par ID 257
Hz
0.00
256
P4.3.3
2
Skip F1 High Limit
See Par ID 256
400.00
Hz
0.00
257
P4.3.4
2
Skip F2 Low Limit
0.00
See Par ID 259
Hz
0.00
258
P4.3.5
2
Skip F2 High Limit
See Par ID 258
400.00
Hz
0.00
259
P4.3.6
2
Skip F3 Low Limit
0.00
See Par ID 261
Hz
0.00
260
P4.3.7
2
Skip F3 High Limit
See Par ID 260
400.00
Hz
0.00
261
Table 29. Energy Savings Calc—P4.4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P4.4.1
2
Currency
0
2122
0 = $
1 = £
2 = €
3 = ¥
4 = Rs
5 = R$
6 = Fr
7 = kr
P4.4.2
2
Energy Cost
Varies
0.00
2123
P4.4.3
2
Data Type
0
2124
0 = Cumulative
1 = Daily Avg
2 = Weekly Avg
3 = Monthly Avg
4 = Yearly Avg
P4.4.4
Energy Savings Reset
2125
0 = Not Reset
1 = Reset
Table 30. Basic Setting—P5.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P5.1.1
1
2
Motor Control Mode
0
287
0 = Freq Control
1 = Speed Control
P5.1.2
1
Current Limit
DriveNomCurr
CT*1/10
DriveNomCurr
CT*2
A
DriveNomCurrCT*2 107
P5.1.3
1
2
V/Hz Optimization
0
109
See Par ID 1679
P5.1.4
1
2
V/Hz Ratio
3
108
0 = Linear
1 = Squared
2 = Programmable
3 = Flux Optimization
P5.1.5
1
2
Field Weakening Point
8.00
400.00
Hz
Varies
289
P5.1.6
1
2
Voltage at FWP
10.00
200.00
%
100.00
290
P5.1.7
1
2
V/Hz Mid Frequency
0.00
See Par ID 289
Hz
Varies
291
P5.1.8
1
2
V/Hz Mid Voltage
0.00
100.00
%
100.00
292
P5.1.9
1
2
Zero Frequency Voltage
0.00
40.00
%
0.00
293