Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
31
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Bypass
Table 36. Basic Setting—P10.1
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P10.1.1
12
Bypass Enable
1
1418
See Par ID 1679
P10.1.2
12
Bypass Start Delay
1
32765
s
1
544
P10.1.3
12
Auto Bypass
1
542
See Par ID 1679
P10.1.4
12
Auto Bypass Delay
0
32765
s
10
543
P10.1.5
12
OverCurrent Bypass Enable
0
547
See Par ID 1679
P10.1.6
12
IGBT Fault Bypass Enable
0
546
See Par ID 1679
P10.1.7
12
4mA Fault Bypass Enable
0
548
See Par ID 1679
P10.1.8
12
UnderVoltage Bypass
Enable
0
545
See Par ID 1679
P10.1.9
12
OverVoltage Bypass Enable
0
549
See Par ID 1679
P10.1.10
12
Motor OverTemp Bypass
Enable
0
1698
See Par ID 1679
P10.1.11
12
UnderLoad Bypass Enable
0
1699
See Par ID 1679
P10.1.12
12
External Bypass Enable
0
1700
See Par ID 1679
P10.1.13
12
Charge Switch Fault Bypass
Enable
0
1701
See Par ID 1679
P10.1.14
12
Saturation Trip Fault Bypass
Enable
0
1702
See Par ID 1679
P10.1.15
12
Under Temp Fault Bypass
Enable
0
1703
See Par ID 1679
P10.1.16
12
EEPROM Fault Bypass
Enable
0
1704
See Par ID 1679
P10.1.17
12
FRAM Fault Bypass Enable
0
1705
See Par ID 1679
P10.1.18
12
Watchdog Fault Bypass
Enable
0
1706
See Par ID 1679
P10.1.19
12
Fan Cooling Fault Bypass
Enable
0
1707
See Par ID 1679
P10.1.20
12
Keypad Com Fault Bypass
Enable
0
1708
0 = Disabled
2 = Enabled
P10.1.21
12
Option Card Fault Bypass
Enable
0
1709
See Par ID 1679
P10.1.22
12
RTC Clock Fault Bypass
Enable
0
1710
See Par ID 1679
P10.1.23
12
Ctrl Board OverTemp Fault
Bypass Enable
0
1711
See Par ID 1679
P10.1.24
12
Speed Search Start Fault
Bypass Enable
0
1712
See Par ID 1679
P10.1.25
12
Fieldbus Fault Bypass
Enable
0
1713
See Par ID 1679