Step 5—Standard Parameter List
30
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 34. Auto Restart—P6.4
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P6.4.1
2
AR Wait Time
1.00
300.00
s
1.00
321
P6.4.2
2
AR Trail Time
0.00
600.00
s
30.00
322
P6.4.3
2
AR Start Function
0
323
0 = Flying Start
1 = Ramp
P6.4.4
2
Undervoltage Attempts
0
10
1
324
P6.4.5
2
OverVoltage Attempts
0
10
1
325
P6.4.6
2
OverCurrent Attempts
0
3
0
326
P6.4.7
2
4mA Fault Attempts
0
10
0
327
P6.4.8
2
Motor Temp Fault Attempts 0
10
0
329
P6.4.9
2
External Fault Attempts
0
10
0
328
P6.4.10
2
Underload Attempts
0
10
0
336
Table 35. Fire Mode—P9
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P9.1
1
2
Fire Mode Function
0
535
0 = Closing Contact
1 = Opening Contact
P9.2
1
2
Fire Mode Ref Select
Function
0
536
0 = Fire Mode Min Frequency
1 = Fire Mode Ref
2 = Fieldbus Ref
3 = AI1
4 = AI2
5 = AI1 + AI2
P9.3
2
Fire Mode Min Frequency
See Par ID 101
See Par ID 102
Hz
15.00
537
P9.4
2
Fire Mode Freq Ref 1
0.0
100.0
%
75.0
565
P9.5
2
Fire Mode Freq Ref 2
0.0
100.0
%
100.0
564
P9.6
Fire Mode Test Enable
2443
See Par ID 1679