Step 5—Standard Parameter List
28
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
P6.1.18
2
Preheat Control Source
31
2160
0 = DigIN:NormallyOpen
1 = DigIN:NormallyClose
2 = DigIN: 1
3 = DigIN: 2
4 = DigIN: 3
5 = DigIN: 4
6 = DigIN: 5
7 = DigIN: 6
8 = DigIN: 7
9 = DigIN: 8
10 = DigIN: A: IO1: 1
11 = DigIN: A: IO1: 2
12 = DigIN: A: IO1: 3
13 = DigIN: A: IO5: 1
14 = DigIN: A: IO5: 2
15 = DigIN: A: IO5: 3
16 = DigIN: A: IO5: 4
17 = DigIN: A: IO5: 5
18 = DigIN: A: IO5: 6
19 = DigIN: B: IO1: 1
20 = DigIN: B: IO1: 2
21 = DigIN: B: IO1: 3
22 = DigIN: B: IO5: 1
23 = DigIN: B: IO5: 2
24 = DigIN: B: IO5: 3
25 = DigIN: B: IO5: 4
26 = DigIN: B: IO5: 5
27 = DigIN: B: IO5: 6
28 = Time Channel 1
29 = Time Channel 2
30 = Time Channel 3
31 = Drive Temperature
32 = SlotA PT100 Temp Channel 1
33 = SlotA PT100 Temp Channel 2
34 = SlotA PT100 Temp Channel 3
35 = SlotA Max PT100 Temp
36 = SlotB PT100 Temp Channel 1
37 = SlotB PT100 Temp Channel 2
38 = SlotB PT100 Temp Channel 3
39 = SlotB Max PT100 Temp
40 = SlotA and SlotB Max PT100
40 =
Temp
P6.1.19
2
Preheat Enter Temp
0.0
19.9
°C
10.0
2161
P6.1.20
2
Preheat Quit Temp
20.0
40.0
°C
20.0
2162
P6.1.21
2
Preheat Output Volt
0.0
20.0
%
2.0
2163
Table 31. Motor—P6.1, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note