Step 5—Standard Parameter List
Variable Speed Drives Series III
LIT-12012996—April 2018
www.johnsoncontrols.com
19
Notes
1
Parameter value can only be changed after the drive has stopped.
2
Parameter value will be set to be default when changing macros.
3
Input function is Level sensed.
4
Input function is Edge sensed.
5
Input function is Edge sensed when using StartP/StopP start logic.
Table 18. Digital Input—P2.2, continued
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P2.2.2
25
IO Terminal 1 Start Signal 1
2
190
0 = DigIN:NormallyOpen
1 = DigIN:NormallyClose
2 = DigIN: 1
3 = DigIN: 2
4 = DigIN: 3
5 = DigIN: 4
6 = DigIN: 5
7 = DigIN: 6
8 = DigIN: 7
9 = DigIN: 8
10 = DigIN: A: IO1: 1
11 = DigIN: A: IO1: 2
12 = DigIN: A: IO1: 3
13 = DigIN: A: IO5: 1
14 = DigIN: A: IO5: 2
15 = DigIN: A: IO5: 3
16 = DigIN: A: IO5: 4
17 = DigIN: A: IO5: 5
18 = DigIN: A: IO5: 6
19 = DigIN: B: IO1: 1
20 = DigIN: B: IO1: 2
21 = DigIN: B: IO1: 3
22 = DigIN: B: IO5: 1
23 = DigIN: B: IO5: 2
24 = DigIN: B: IO5: 3
25 = DigIN: B: IO5: 4
26 = DigIN: B: IO5: 5
27 = DigIN: B: IO5: 6
31 = RO1 Function
32 = RO2 Function
33 = RO3 Function
34 = Virtual RO1 Function
35 = Virtual RO2 Function
P2.2.3
25
IO Terminal 1 Start Signal 2
3
191
See Par ID 190
P2.2.4
1
2
IO Terminal 2 Start Stop
Logic
0
2206
See Par ID 143
P2.2.5
25
IO Terminal 2 Start Signal 1
2
2207
See Par ID 190
P2.2.6
25
IO Terminal 2 Start Signal 2
3
2208
See Par ID 190
P2.2.7
12
Thermistor Input Select
0
881
0 = Digital Input
1 = Thermistor Input
P2.2.8
23
Reverse
0
198
See Par ID 190
P2.2.9
23
Ext. Fault 1 NO
4
192
See Par ID 190
P2.2.10
23
Ext. Fault 1 NC
1
193
See Par ID 190
P2.2.11
2
Ext. Fault 1 Text
0
2297
0 = External Fault
1 = Vibration Cut out
2 = High Motor temp
3 = Low Pressure
4 = High Pressure
5 = Low Water
6 = Damper Interlock
7 = Run Enable
8 = Freeze Stat Trip
9 = Smoke Detect
10 = Seal Leakage
11 = Rod Breakage
P2.2.12
23
Ext. Fault 2 NO
0
2293
See Par ID 190