Jetter AG
Electrical connection | 6
User Manual – JetControl 365MC
34 / 148
Y-cable (splitter cable)
INFO
Y-cable (splitter cable)
To use both CAN buses, connect a Y-cable (splitter cable) to port X19.
One end of the Y-cable (CAN 1) lets you use either the JX2 system bus protocol,
or the CANopen protocol (configuration via R 200002077). The other end of the
Y-cable (CAN 2) lets you use the CANopen protocol. The functions of the pro-
gramming interface CANopen STX API implement the CANopen protocol. For
more information, see the application-oriented manual CANopen STX API.
You can order the Y-cable separately as an
.
A
A
B
B
C
C
1
1
1
2
2
2
3
3
3
4
4
4
5
5
5
6
6
6
7
7
7
8
8
8
9
9
9
Fig. 11:
Y-cable (splitter cable) for the CAN bus interface
Position
Component
Description
A
Male sub-D connector,
9-pin
For connection to BUS OUT
B
Female Sub-D connec-
tor, 9-pin
For connection to BUS IN (CAN 1)
C
Female Sub-D connec-
tor, 9-pin
For connection to BUS IN (CAN 2)
Male Sub-D
Connector (A)
The 9-pin Sub-D connector of the Y-cable has the following pin assignment:
Pin
Signal
Description
1
CMODE0
Commissioning
2
CAN-L
Data signal CAN 1
3
GND
Reference potential
4
CMODE1
Commissioning
6
CAN-L_2
Data signal CAN 2
7
CAN-H
Data signal CAN 1
8
CAN-H_2
Data signal CAN 2