Jetter AG
Technical specifications | 4
User Manual – JetControl 365MC
22 / 148
4.6 EMI values
4.6.1 Housing
Emitted
interference
Parameter
Values
Standards
Frequency band
30 MHz … 230 MHz
DIN EN 61000-6-3
DIN EN 61131-2
DIN EN 55011
Limit value
30 dB (µV/m) at 10 m
distance
Frequency band
230 MHz … 1,000 MHz
Limit value
37 dB (µV/m) at 10 m
distance
Class B
Tab. 14:
Emitted interference
Immunity to
interference
Parameter
Values
Standards
Magnetic field with mains frequency
Frequency
50 Hz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-8
Magnetic field
30 A/m
RF field, amplitude-modulated
Frequency band
80 MHz ... 2 GHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-3
Test field strength
10 V/m
AM 80 % at 1 kHz
Criterion A
ESD
Discharge through air
Test peak voltage
8 kV
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-2
Contact discharge
Test peak voltage
4 kV
Criterion A
Tab. 15:
Immunity to interference
4.6.2 Shielded data and I/O lines
Immunity to
interference
Parameter
Values
Standards
RF field, asymmetric, amplitude modulated
Frequency band
0.15 MHz … 80 MHz
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-6
Test voltage
10 V
AM 80 % at 1 kHz
Source impedance
150 Ω
Criterion A
Bursts
Test voltage
1 kV
DIN EN 61000-6-2
DIN EN 61000-6-2
DIN EN 61000-4-4
tr/tn 5/50 ns
Repetition frequency
5 kHz
Criterion A
Surge voltages, asymmetric, line to earth
Common-mode
interference
tr/th 1.2/50 µs
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-5
1 kV
Tab. 16: