Jetter AG
Technical specifications | 4
User Manual – JetControl 365MC
21 / 148
Connected
JX3 IO modules
Parameter
Description
Logic voltage
Current consumption
I
5V
= max. 1,200 mA
Power consumption
6 W max.
Additional voltage
Current consumption
I
24 V
= max. 750 mA
Power consumption
18 W max.
Tab. 11:
JX3 IO modules on the system bus
4.4 Real-time clock
Parameter
Description
Power reserve
(if the controller was pre-
viously switched on for at
least 1 hour)
Minimum
1 week
Typically
2 weeks
Deviation
maximum
1 minute per month
Tab. 12:
Real-time clock
4.5 Environmental conditions
Parameter
Description
Standards
Operating temperature
0 °C … +50 °C
DIN EN 61131-2
Storage temperature
-40 °C … +70 °C
DIN EN 60068-2-1
Air humidity
10 % … 95 %,
non-condensing
DIN EN 60068-2-2
Max. operating altitude
2,000 m above sea level
DIN EN 61131-2
Corrosion immunity and
chemical resistance
No special protection against corrosion. Ambient air
must be free from higher concentrations of acids,
alcaline solutions, corrosive agents, salts, metal
vapors, and other corrosive or electroconductive
contaminants.
Degree of pollution - Elec-
tronics
Degree of pollution 2
DIN EN 61131-2
Usually, the pollution is non-conductive. However,
temporary conductivity due to condensation may
occur.
Tab. 13:
Environmental conditions