8.6 Manual Programming with internal limit switches detection
Follow the steps to perform the manual programming with internal limit switches detection. It is necessary
to have the internal limit switches detection activated
(P1E parameter)
:
1. Door is in the totally closed position
2. Press PROG pushbutton to enter programming mode
3. The PROG Led will turn on
4. Press START pushbutton or a programmed transmitter to program the maneuver
5. The door opens two seconds and stops
6. The door closes automatically until the closed position
7. The door stops
8. The door opens automatically until a mechanical stop or a limit switch is reached
9. The door stops
10. Wait to program the desired autoclose time
11. Press START pushbutton to close the door
12. The door closes until a mechanical stop or a limit switch is reached
13. The door stops
14. The PROG Led turns off
15. The programming is finished