GAMMA VERSUS MANUAL
18
COD. 1257066 Gamma VERSUS Manual v1.13
4.3 Switch parameters
The switch parameters allow assigning different functions to each option of the switch. Each switch input
(option) can have different values; they are indicated on the third column of the following table.
If there is a physical switch on the board with one of the following parameters associated, it will be taken into
account always. That means, if option 1 of the physical switch on the board has assigned the function
Autoprogramming and it is at ON, and the parameter 01 (Autoprogramming) is at OFF, the control panel will
take the value Autoprogramming at ON.
4.3.1 Switch parameters
Num Switch
Available values - description
54
Switch 1
0
NO FUNCTION
The switch has not got a defined function
1 AUTOPROGRAM
MING
Enables the autoprogramming function
2
AUTOCLOSE
Enables the autoclose function
3 NOSTOP
ON
OPENING
Enables the non inversion at opening function
4
SLOW SPEED
Enables the slow speed
5 ELECTROLOCK Disables
the electrolock function
6 INH.4CM
S.EDGE.CL
Enables the safety edge inhibition function during the last 4cm of the closing
movement.
7
DEAD MAN
Enables the deadman function
8 SEC.CL
INHIBITION
Enables the closing safety contact inhibition function.
9
RSENS CONFIG
Enables the RSENS mode.
10
RBAND CONFIG
Enables the RBAND mode.
11 TIME/HALL
CONFIG
Configures:
1 - ON: Time function;
2 - OFF: HALL function
12
SEC.CL TEST
Enables the closing security contact autotest
13
SEC.OP TEST
Enables the opening security contact autotest
14
PRE-FLASH
Enables the pre-flash function
15 CLOSING
BY
SEC.CL
Enables the closing security contact
16 COURTESY
LIGHT/FLASH
Configures:
1 - ON: garage light output;
2 - OFF: flash output
17 TEST
PRESSURE
SWITCH
Configuration test pressure switch function.
18 INH.OP.PRESSU
RE SW
Enables the inhibition function of the pressure switch during the opening
sequence.
19 SEC.CL
OPEN
REF
Configuration of close security contact as opening reference function.
20 AUTO
DETECT.FC.
Configuration of the autodetection of limit switches by current (AC motors).
21 REVERSE
STRIKE
Configuration of the reverse strike at open.
22
SEC. OPEN &
CLOSE
Configuration closing security contact as closing/opening security contact
function
23 OPEN
DM
OR
AUTO (*)
Configuration opening sequence in deadman in comercial mode. In OFF the
opening is made by deadman
24 COMMERCIAL
MODE (*)
Configuration commerce and garage mode functions
25 INVERT
BOLLARD
OUTPUT
Output configurated as inverted bollard output.
26 TWO
MOTORS
MODE
Enables the function to use control panel to control two motors.
27 PULSE(OFF)-
C.LIGHT(ON)
Configuration output is PULSE 2sec (OFF) or COURTESY LIGHT (ON) function
55
Switch 2
56
Switch 3
57
Switch 4
58
Switch 5
59
Switch 6
5A
Switch 7
5B
Switch 8
Содержание GAMMA VERSUS M20
Страница 6: ...GAMMA VERSUS MANUAL 6 COD 1257066 Gamma VERSUS Manual v1 13 2 3 Sectional door 2 4 Folding door...
Страница 7: ...GAMMA VERSUS MANUAL 7 COD 1257066 Gamma VERSUS Manual v1 13 2 5 Rolling door 2 6 Fast door...
Страница 75: ...GAMMA VERSUS MANUAL 75 COD 1257066 Gamma VERSUS Manual v1 13...
Страница 78: ...GAMMA VERSUS MANUAL 78 COD 1257066 Gamma VERSUS Manual v1 13...
Страница 79: ...GAMMA VERSUS MANUAL 79 COD 1257066 Gamma VERSUS Manual v1 13...
Страница 108: ...GAMMA VERSUS MANUAL 108 COD 1257066 Gamma VERSUS Manual v1 13 13 SAFETY INSTRUCTIONS FOR MAINTENANCE...