GAMMA VERSUS MANUAL
15
COD. 1257066 Gamma VERSUS Manual v1.13
synchronism or closed door. The ground is normally point 0. In the case of
operations by time, the entire opening movement operation duration is
indicated. The panel returns the count in slow speed units, the programme
recalculates by adding the slow and normal speeds, multiplied by the
normal/slow ratio factor, as applicable.
34
Closing stop point 1000
Stop point for the closure movement. In the case of operations by pulses
and on most panels, this is position value 0. It will be of no use for
controlling the position of the door. In the case of operations by time, the
entire closure movement operation duration is indicated. The panel
returns the count in slow speed units, the programme recalculates by
adding the slow and normal speeds, multiplied by the normal/slow ratio
factor, as applicable.
35
Open slow start pt. 1000
Opening movement point where the slow speed is started in order to be
able to slow down the door. In the case of operations by pulses, this is
normally the number of pulses with regards to the ground (closed door). In
the case of operations by time, the programmer will indicate the time from
the start of opening to this point.
36
Close slow start pt. 1000
Closure movement point where the slow speed is started in order to be
able to slow down the door. In the case of operations by pulses, this is
normally the number of pulses with regards to the ground (closed door). In
the case of operations by time, the programmer will indicate the time from
the start of closure to this point.
37
Open Ped.stop
point
1000
Stop point for the door during pedestrian opening movements.
38
Close Ped.stop
point
1000
Stop point for the door during pedestrian closure movements.
39
Open Ped.slow
start pt.
1000
Opening movement point where the slow speed is started in order to be
able to slow down the door on pedestrian opening.
3A
Close Ped.slow
start pt.
1000
Closing movement point where the slow speed is started in order to be
able to slow down the door on pedestrian opening.
3B
SEC.CL inhib.point 1000
Point at which security contact inhibition is started during the closing
movement.
3C
BJump time/pulses
open
1000
Distance run as opening Back Jump. It is normally a small distance in
pulses or time.
3D
Bjump time/pulses
close
1000
Distance run as closure Back Jump. It is normally a small distance in
pulses or time.
3E
Max.time/pulses to
limit
1000
Number of pulses or time to be added to the opening and closure
movement to search for the reference, i.e. to reach the end of run or
mechanical stop memorised during programming.
3F
Inertia opening
1000
Number of pulses that the door has run with the motor at a standstill due to
inertia during opening operations.
40
Inertia closing
1000
Number of pulses that the door has run with the motor at a standstill due to
inertia during closure operations.
41
Autoclose value
10
Auto-close time.
42
Inhib.zone start
point
1000
Size of the inhibition zone of any safety device at the end of the maneuver.
43
Imax normal speed 10
Maximum current measured during programming at normal speed. This
will normally be the current limit that the panel will accept during
operations at normal speed.
44
Imax low speed
10
Maximum current measured during programming at slow speed. This will
Содержание GAMMA VERSUS M20
Страница 6: ...GAMMA VERSUS MANUAL 6 COD 1257066 Gamma VERSUS Manual v1 13 2 3 Sectional door 2 4 Folding door...
Страница 7: ...GAMMA VERSUS MANUAL 7 COD 1257066 Gamma VERSUS Manual v1 13 2 5 Rolling door 2 6 Fast door...
Страница 75: ...GAMMA VERSUS MANUAL 75 COD 1257066 Gamma VERSUS Manual v1 13...
Страница 78: ...GAMMA VERSUS MANUAL 78 COD 1257066 Gamma VERSUS Manual v1 13...
Страница 79: ...GAMMA VERSUS MANUAL 79 COD 1257066 Gamma VERSUS Manual v1 13...
Страница 108: ...GAMMA VERSUS MANUAL 108 COD 1257066 Gamma VERSUS Manual v1 13 13 SAFETY INSTRUCTIONS FOR MAINTENANCE...