Addr. Description
Setting range
Type Unit Presetting
000
UMG96S Device address
1 .. 255
CHAR
-
1
001
Baud rate (RS232 and RS485)
0 .. 2
CHAR
1)
kbps
0
002
Input/Output 1, Type
0 .. 6
CHAR
2a)
-
0
003
Input/Output 2, Type
0 .. 6
CHAR
2b)
-
0
004
Pulse valence, Digital output 1
0 .. 100000
PULS
Wh
1,00
5)
006
Pulse valence, Digital output 2
0 .. 100000
PULS
varh
1,00
5)
008
Delete min. and max. values
0 .. 1
CHAR
-
0
009
Delete energy
0 .. 1
CHAR
-
0
010
Min. pulse duration, Digital output 1/2
5 .. 99
CHAR
3)
ms
5=50ms
011
User password
0 .. 999
INT
-
000
012
LCD contrast
0 .. 7
CHAR
-
3
013
Comparator 1A, limit
-999999999 ..
999999999
LONG
0
015
Comparator 1A, measured value
0 .. 999
INT
6)
000
016
Comparator 1A, Min. on time
1 .. 899
INT
Sec.
1
017
Comparator 1A, Operator
0, 1
CHAR
4)
0
018
Comparator 1B, limit
-999999999 ..
999999999
LONG
020
Comparator 1B, measured value
0 .. 999
INT
6)
021
Comparator 1B, min. on time
1 .. 899
INT
Sec.
1
022
Comparator 1B, Operator
0, 1
CHAR
4)
0
023
Comparator 1C, limit
-999999999 ..
999999999
LONG
025
Comparator 1C, measured value
0 .. 999
INT
6)
026
Comparator 1C, min. on time
1 .. 899
INT
Sec.
1
027
Comparator 1C, Operator
0, 1
CHAR
4)
0
028
Comparator 2A, limit
-999999999 ..
999999999
LONG
030
Comparator 2A, measured value
0 .. 999
INT
6)
031
Comparator 2A, min. on time
1 .. 899
INT
Sec.
1
032
Comparator 2A, Operator
0, 1
CHAR
4)
0
033
Comparator 2B, limit
-999999999 ..
999999999
LONG
035
Comparator 2B, measured value
0 .. 999
INT
6)
036
Comparator 2B, min. on time
1 .. 899
INT
Sec.
1
037
Comparator 2B, not/inverted
0, 1
CHAR
4)
0
038
Comparator 2C, limit
-999999999 ..
999999999
LONG
1)
0 = 9,6kBit/s; 1 = 19,2kBit/s; 2 = 38.4kBit/s
2a)
0 = Pulse output, 1 = digital output, 2 = analog output, 3 = digital input,
4 = Profibus-Remote output, 5 = HT/NT changeover, real energie,
6 = HT/NT changeover, real energie and reactive energie.
2b)
0 = Pulse output, 1 = digital output, 2 = analog output, 3 = digital input,
4 = Profibus-Remote output, 5 = HT/NT changeover, reactive energie,
6 = HT/NT changeover, real energie and reactive energie.
3)
Min. pulse duration = setting range * 10 [ms]
4)
0 = higher than, 1 = smaller than
5)
Reading/writing 100=1,00
6)
0 = Comparator not used, 1 = remote, 200-424 = measured values
Parameter list