Page 62
Pulse output
Each
Digit output
can be used as pulse output.
Pulse output 1 can transmit
real energy Wp
and
pulse output 2 can transmit
reactive energy
Wq
.
For both pulse outputs, the
pulse valence
can
be set seperately via the parameter addresses
004 and 006.
The
Minimum pulse duration
is valid for both
pulse outputs, and can be set via parameter
address 010.
UMG96S
12
13
11
R
J
1
1
S
le
e
v
e
14
15
TXD
GND
RXD
A
B
Input/Output 2 (003)
Pulse output Wp (003 =0)
Digital output
(003 = 1)
Analog output (003 = 2)
Digital input
(003 = 3,5)
Profibus-Remote (003 = 4)
Input/Output 1 (002)
Pulse output Wp (002 =0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3,5)
Profibus-Remote (002 = 4)
C
o
m
p
a
ra
to
r
g
ro
u
p
1
C
o
m
p
a
ra
to
r
g
ro
u
p
2
Basic PCB
RS485 (MODBUS RTU)
Interface
RS232 (MODBUS RTU)
Interface
S
e
ri
a
l
in
te
rf
a
c
e
The collected pulses within a second will be
transmitted with the programmed pulse duration
and a maximum frequency of 10Hz.
If the measured energy exceeds the set pulse
valence, so the maximum frequency for the
pulse output would be exceeded, the remaining
pulses are stored and given out later. Stored
pulses get lost during a net breakdown.