Voltage versions
The UMG96S takes the measurement voltage
as operating voltage and can be delivered in the
versions 150V and 300V. The delivered version
is indicated on the type plate of UMG96S.
Please ensure, that the local net conditions
match the numbers on type plate before con-
nection.
300V standard version
In
300V standard version
, the UMG96S can
measure voltage up to 300VAC against ground.
At leats one phase (L) of the UMG96S and the
neutral N must be connected and the connected
voltage must be within the measurement and
operation voltage range.
The
measurement and operation voltage
range
of devices without additional PCB and for
devices with additional PCB 1 (analogue output)
are:
Measuring range L-N
: 50 .. 300V AC
Measuring range L-L
: 87 .. 520V AC
Operating voltage range L-N
: 85 .. 300V AC
The measurement and operating voltage range
for devices with additional PCB 2 (Profibus) are:
Measuring range L-N
: 50 .. 300V AC
Measuring range L-L
: 87 .. 520V AC
Operating voltage range L-N
:140.. 300V AC
150V special version
In
150V special version,
the UMG96S can
measure voltage up to 300VAC against ground.
At least 2 phases (L) of the UMG96S must be
connected, and the connected voltage must be
within the measurement and operation voltage
range.
Measuring range L-N
: 25 .. 140V AC
Measuring range L-L
: 40 .. 260V AC
Operating voltage range L-L
: 85 .. 260V AC
Attention!
Voltage, which is above the allowed
range can damage the device.