Page 64
Diagr. Maximum pulse frequency at minimum
pulse duration 50ms.
2.) Determine minimum pulse duration
The UMG96S can transmit pulses with a fre-
quency of up to 10Hz.
The data collecting device can retrieve pulses
with a frequency of 50Hz in this example. The
minimum pulse duration at UMG96S can be set
to 50ms.
Minimum pulse duration Addr.010 = 005
Example: Program pulse output
The UMG96S shall measure real energy in a
distribution, and transmit it via pulse output to a
data collecting device. The distribution provides
a real power of 400kW. The data collecting de-
vice can retrieve pulse frequencies up to 50Hz.
At UMG96S, the
pulse output
, the
minimum
pulse duration
and the
pulse valence
must be
programmed.
Input/Output 2 (003)
Pulse output Wp (003 =0)
Digital output
(003 = 1)
Analog output (003 = 2)
Digital input
(003 = 3,5)
Profibus-Remote (003 = 4)
Input/Output 1 (002)
Pulse output Wp (002 =0)
Digital output
(002 = 1)
Analog output (002 = 2)
Digital input
(002 = 3,5)
Profibus-Remote (002 = 4)
12
13
11
UMG96S
+
1.) Select pulse output
Assign terminal 12 to the function pulse output.
Input/Output 1 Addr.002=0
Pulse
50ms
Pulse pause
50ms
100ms => 10Hz
Minimum pulse duration
Diagr: Connection example for the connection of
the terminals 11 and 13 as pulse output.
+
-
230V AC
24V DC
External
power supply
+24V=
11
12
13
UMG96S
Digital/pulse outputs
1,5k
Data col-
lection